Users Manual 33
PART 1 AD268 7. Troubleshooting
7.2 Troubleshooting
The table below shows the trouble and its remedy.
Trouble Module
status info LED Module operation Cause Remedy
Input type
setting error Bit 7 is ON ON
(if the error
occurs in all
channels, it
is OFF)
The error channel
stops the
conversion. The A/D
conversion data is 0.
Invalid input ty pe
parameter was set. Set the correct
input type
parameter.
Analog signal
wire breakage
(4-20mA only)
Bit 8 is ON ON The A/D conversion
data of the channel
is 0.
In the 4-20mA
input, less than
4mA signal is input.
Check the analog
signal wire.
Analog signal
limit over Bit 9 is ON ON The A/D conversion
data of the channel
is limited by the limit
value.
Analog input signal
is out of the range. Check t he signal
source (sensor).
MPU error Bit A is ON OFF The A/D conversion
is stopped. Internal proc essor
operation is not
normal.
Execute reset
command, or
cycle power off
and on.
ROM error Bit B is ON OFF The A/D conversion
is stopped. EEPROM data
error is detected. Cycle power o ff
and on.
DP-RAM error Bit C is ON OFF The A/D conversion
is stopped. Buffer memory
access error is
occurred.
Cycle power off
and on.
External 24V
error Bit E is ON O F F T he A/ D conv ersion
is stopped. Internal ±15V
voltage is not
normal.
Check the
external 24Vdc
power supply.