54 Analog I/O Modules (AD268 / DA264 / TC218)
6. Parameters PART 2 DA264
Analog output read-back value:
(H8008 to H800B)
These data show the D/A conversion data after processing the offset calibration.
Module status:
(H800C to H800F)
These data show the DA264s operation status.
Bit position FEDCBA9876543210
00000 00
Bit Name Description
0 to 2 Output type Shows the output type.
000 (0) = 0 to 5V/0 to 20mA
001 (1) = 0 to 10V
010 (2) = 1 to 5V/4 to 20mA
100 (4) = ±5V
101 (5) = ±10V
3 to 4 - Reserved
5 to 7 Hold mode Shows the output mode, clear mode (normal) or hold mode.
101 = Hold mode
Other than above = Clear mode
8 Output type
setting error 1 when the output type designation is inval id.
9 to C - Reserved
D Output limit 1 when the D/A conversion data i s limited because of the range
over.
E External 24V error 1 when the external 24Vdc is not normal.
F- Reserved