ICC
BO5...... Enables or disables process (PID) feedback control. Note that this object
does not activate (turn on) feedback control. It only enables or disables feedback control once it has already been activated. ASD parameter FA06, bit#5.
BO6...... Communication interface frequency priority selection. Allows the frequency
command from the interface card to be used by the drive without having to set the Frequency Mode parameter. Refer to the Toshiba documentation regarding "Command Mode and Frequency Mode Control" for detailed information pertaining to the frequency source hierarchy and the use of overrides. ASD parameter FA06, bit#14.
BO7...... Communication interface command priority selection. Allows commands
(BO1, BO2, and BO5) from the interface card to be used by the drive without having to explicitly set the Command Mode parameter. Refer to the Toshiba documentation regarding "Command Mode and Frequency Mode Control" for detailed information pertaining to the command source hierarchy and the use of overrides. ASD parameter FA06, bit#15.
BO8...... Output terminal data out 1. Any programmable output terminals that are
configured to output “specified data output 1” will follow the value of this BO. ASD parameter FA50, bit#0.
BO9...... Output terminal data out 2. Any programmable output terminals that are
configured to output “specified data output 2” will follow the value of this BO. ASD parameter FA50, bit#1.
BO10.... Output terminal data out 3. Any programmable output terminals that are
configured to output “specified data output 3” will follow the value of this BO. ASD parameter FA50, bit#2.
Analog Input Objects
AI1........ Output frequency in 0.01Hz units. ASD parameter FD00.
AI2........ Load current in 0.01% units (10000=100.00%=drive's rated current). ASD
parameter FE03.
AI3........ Output voltage in 0.01% units (10000=100.00%=drive's rated voltage).
ASD parameter FE05.
AI4........ Input power consumption (drive+motor) in 0.01kW units. ASD parameter
FE29.
AI5........ Indicates the signal level currently being applied to the ASD's RR analog
input terminal. This can be used to monitor such items as feedback sensor outputs and other process variables. Expressed in 0.01% units (10000=100.00%=input rated value). ASD parameter FE35.
AI6........ Similar to AI5, this object indicates the signal level currently being applied to
the ASD's VI/II analog input terminal. ASD parameter FE36.
AI7........ Similar to AI5, this object indicates the signal level currently being applied to
the ASD's RX analog input terminal. ASD parameter FE37.