13.2.4 ControlLogix Example: I/O Messaging
This section will demonstrate how to setup and use an EtherNet/IP I/O connection via
1)Switch to offline mode.
2)Right click on the
3)Choose “Generic Ethernet Module” in the Select Module dialog box and click “OK”. Refer to Figure 77.
Figure 77: Adding a New Generic Ethernet Module
4)The module properties dialog box will open (refer to Figure 78). Enter a Name and Description which will allow easy identification of the drive on the network (the tags created in RSLogix 5000 will be derived from this Name). Because all drive data is stored as
In the “Connection Parameters” portion of the dialog box, enter the following information:
Input: The Input Assembly is the collection of monitor data that is produced by the interface card and is received as an input to the PLC. Its structure is defined by the Produced Register Configuration as described in section 10.8.4. The Input Assembly Instance must be set to 150 when connecting to the vendor- specific I/O assembly instances (or 70/71 when using the ODVA AC/DC drive profile), and the size must be set to the number of
75