ICC

AI8........ Indicates the present fault code. Under normal operation (no faults), this

value will be 0. ASD parameter FC90.

Analog Output Objects

AO1...... Sets the drive's frequency command in 0.01Hz units (e.g. 4000 = 40.00Hz).

Note that the drive will only use this value as its active frequency command if the Frequency Mode parameter is set to “Communication Option Input Enabled ", or if the "frequency override" bit (BO6) is ON. Although the adjustment range for this object is 0-40000 (0.00Hz-400.00Hz), the actual frequency command will be internally limited by the Upper Limit Frequency and Lower Limit Frequency parameters. ASD parameter FA07.

AO2...... Adjusts the FM analog output voltage if the “FM terminal meter selection”

parameter is set to a value of 31 (communication data output). Range is 0- 2047 = 0-100%. ASD parameter FA51.

AO3...... Adjusts the AM analog output voltage if the “AM terminal meter selection”

parameter is set to a value of 31 (communication data output). Range is 0- 2047 = 0-100%. ASD parameter FA52.

112