configured to use the network frequency command as its master frequency command, it will ramp to 50.00Hz.
If timeout/failsafe processing is not desired, just set the “register” fields for all indexes to 0 (disabled). This is the default condition.
“DEC” and “HEX” selection buttons are also available, and allow changing the “value” column data display and entry radix between decimal and hexadecimal formats, respectively. These buttons provide the ability to interact with the various drive registers in their most natural radix (e.g. a hexadecimal command word vs. a decimal frequency command value).
10.7.6 Submitting Changes
Whenever any of the configuration elements has been changed, the “submit” button located in the
Note that because these configuration elements are read from the filesystem only when the interface card boots up, the act of submitting configuration
changes will also reset the interface card. Please allow 30 seconds for the interface card to reboot, at which time it will then be operating with the
38