REQUIREMENT

SMMS-i

Installation Manual

REQUIREMENT

For a welding work of the refrigerant pipes, be sure to use nitrogen gas in order to prevent oxidation of the inside of the pipes; otherwise clogging of the refrigerating cycle due to oxidized scale may occur.

Use clean and new pipes for the refrigerant pipes and perform piping work so that water or dust does not contaminate the refrigerant.

Be sure to use a double spanner to loosen or tighten the flare nut. If a single spanner is used, the required level of tightening cannot be obtained. Tighten the flare nut with the specified torque. (If it is hard to loosen or tighten the flare nut of the balance pipe or packed valve of the liquid side with a double spanner, loosen or tighten the flare nut while holding the valve mounting plate with a spanner.)

SMMS-i

 

 

 

 

Installation Manual

Type

Pipe

 

Draw-out forward

 

Draw-out downward

 

diameter

 

 

 

 

 

 

 

 

 

 

 

Cut the L-shaped pipe at the horizontal straight

Cut the L-shape pipe at the vertical straight

 

 

section, then braze the supplied attachment

section, then braze the supplied attachment

 

 

pipe, and the socket and pipe procured locally. pipe, and the socket and pipe procured locally.

 

 

 

Gas

 

 

 

MAP140

Ø28.6

Liquid

pipe

Liquid

Gas pipe

Gas

Gas pipe

MAP160

pipe

pipe

 

 

Attachment pipe

Balance

Attachment

pipe

 

 

Balance

 

 

 

Socket

pipe

pipe

 

 

 

pipe

 

Socket

 

 

 

 

 

 

Outer dia. of

Tightening torque (N•m)

copper pipe

 

 

 

6.4 mm

14 to 18 (1.4 to 1.8 kgf•m)

 

 

9.5 mm

33 to 42 (3.3 to 4.2 kgf•m)

 

 

12.7 mm

50 to 62 (5.0 to 6.2 kgf•m)

15.9 mm

63 to 77 (6.3 to 7.7 kgf•m)

 

 

Packed valve of balance pipe

Ball valve of gas side

Packed valve of liquid side

Pipe

Pipe

Section

 

to be cut

 

Section

 

 

to be cut

 

Extruding margin of copper pipe with flare machining: B (Unit: mm)

Copper pipe outer

When using R410A

When using

B

dia.

tool

conventional tool

 

9.5

 

 

 

12.7

0 to 0.5

1.0 to 1.5

 

15.9

 

 

 

Pipe connection method of valve at the gas side (Example)

Type

Pipe

 

Draw-out forward

 

 

Draw-out downward

 

diameter

 

 

 

 

 

 

 

 

 

 

 

 

 

Cut the L-shaped pipe at the horizontal straight

Cut the L-shaped pipe at the vertical straight

 

 

section, then braze the supplied attachment

section, then braze the supplied attachment

 

 

pipe and the socket and pipe procured locally.

pipe and the socket and pipe procured locally.

 

 

 

 

Gas

 

 

 

MAP080

Ø22.2

Liquid

Gas pipe

pipe

Liquid

Gas pipe

Gas

MAP100

pipe

Attachment

 

pipe

 

 

 

 

Attachment

pipe

 

 

Balance

pipe

 

Balance

 

 

 

Socket

 

pipe

 

 

 

pipe

 

pipe

Socket

 

 

 

 

 

 

 

 

 

 

 

Pipe

 

 

Pipe

Section

 

 

 

 

 

 

to be cut

 

 

 

 

 

 

 

 

 

 

 

Section to be

 

 

 

 

 

 

 

cut

 

 

 

 

 

Cut the L-shaped pipe at the horizontal straight

Cut the L-shaped pipe at the vertical straight

 

 

section, then braze the supplied attachment

section, then braze the supplied attachment

 

 

pipe and the socket and pipe procured locally. pipe and the socket and pipe procured locally.

 

 

Liquid

 

Gas

Liquid

 

 

MAP120

Ø28.6

Gas pipe

pipe

Gas pipe

Gas

pipe

 

pipe

 

 

 

 

 

 

 

 

 

Balance

Attachment pipe

 

Balance

Attachment

pipe

 

 

pipe

 

 

pipe

 

 

 

Socket

 

pipe

 

 

 

 

 

 

 

 

 

 

 

 

Socket

Section

 

 

 

Pipe

 

 

 

 

 

 

 

Pipe

to be cut

 

 

 

 

 

 

 

 

 

 

Section to be

 

 

 

 

 

 

 

 

 

 

 

 

 

cut

 

 

 

Extruding margin of copper pipe with flare tools: A (Unit: mm)

Copper pipe outer dia.

A-+00.4

 

 

 

A

 

9.5

13.2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12.7

16.6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

15.9

19.7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*When using the conventional flare tool, to connect R410A pipes with flaring, make a margin approx. 0.5mm longer than that of an R22 pipe so that the flare size matches the one specified. It is convenient to use a copper pipe gauge for size adjustment of the extruding margin.