„Resetting the address

SMMS-i

3 Push the SET button.

Installation Manual

„Resetting the address

SMMS-i

Installation Manual

The address of one of the indoor units connected to the selected refrigerant line is indicated on the LCD display and the fan and louvers of the unit are activated.

At first, the current indoor unit address is displayed in SET DATA.

(No system address is indicated.)

 

CODE No.

SET DATA SETTING

 

UNIT

No.

R.C.

No.

TEMP.

ON / OFF

(Resetting to the factory

default (address undecided))

Method 1

Clearing each address separately using a wired remote controller.

Set the system address, indoor unit address and group address to “0099” using a wired remote controller. (For the setting procedure, refer to the address setting procedures using the wired remote controller on the previous pages.)

Method 2

Clearing all the indoor unit addresses on a refrigerate line at

Header

 

Follower unit

unit

 

U3 U4

U3 U4

U1 U2

U5 U6

U1 U2

U5 U6

Header unit

U3 U4

U1

U2

 

U5

U6

 

 

 

 

 

Follower unit

U3 U4

U1 U2

U5 U6

 

 

 

 

 

 

 

 

Central control

 

 

 

 

 

 

 

 

controller

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

U1

U2

 

Header

 

 

 

 

 

U3

U4

 

 

 

 

 

 

 

 

 

 

unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

U3

U4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

U1

U2

 

 

U5

U6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TIMER SET

4

 

TIME

FILTER

 

 

RESET TEST

SET CL

8

 

 

Finish

 

 

6

once from the outdoor unit.

1 Turn off the refrigerant line to reset to the factory default and set the header outdoor unit of the line as below.

1) Disconnect the relay connectors between the

[U1, U2] and [U3, U4] terminals.

U1

U2

 

 

 

U1

U2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A

B

 

 

 

A

B

 

Remote

 

Remote

controller

 

controller

U1 U2

A B

Remote controller

U1 U2

A B

U1 U2

A B

Remote controller

5, 7

Press to finish setting.

(Leave them as they are if they have already

been disconnected.)

2) Turn on dip switch 2 of SW30 on the interface

(Resetting to the factory Indoor units to have their addresses initialized

4 Push the TIME default (address undecided)) / – 28 – buttons repeatedly to change the value of the indoor unit address in SET DATA.

Change the value in SET DATA to that of a new address.

5 Push the SET button to confirm the new address on SET DATA.

6 Push the Manual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual background button (left side of the button) repeatedly to select another address to change. Each time you push the button, the indoor unit numbers in a refrigerant line are indicated one after another. Only the fan and louvers of the selected indoor unit are activated.

Repeat steps 4 to 6 to change the indoor unit addresses so as to make each of them unique.

7 Push the SET button.

(All the segments on the LCD display light up.)

8 Push the TEST button to finish the procedure.

P.C. board of the header outdoor unit if the

switch is OFF.

(Leave it as it is if it has already been set to

ON.)

2 Turn on the indoor and outdoor units of the refrigerant line for which you want to initialize the addresses. About one minute after turning on the power, confirm that the 7-segment display on the header outdoor unit indicates “U.1. - - -” and operate the interface P.C. board on the header outdoor unit of the refrigerant line as follows.

SW01

SW02

SW03

SW04

Clearable addresses

2

1

2

Confirm that the 7-segment display indicates

System/indoor unit/group address

“A.d.buS” and turn SW04 ON for more than five

 

 

 

seconds.

 

2

2

2

Confirm that the 7-segment display indicates

Central control address

“A.d.nEt” and turn SW04 ON for more than five

 

 

 

seconds.

 

3 Confirm that the 7-segment display indicates “A.d. c.L.” and set SW01, SW02 and SW03 to 1, 1, 1 respectively.

4 After a time “U.1.L08” appears on the 7-segment display if the address clearing has been completed successfully.

If the 7-segment display indicates “A.d. n.G.”, the outdoor unit may still connected with other refrigerant lines. Check the connection of the relay connectors between [U1, U2] and [U3, U4].

NOTE

Take care to carry out the procedure above correctly; otherwise, addresses in other refrigerate lines may also be cleared.

5 Set the addresses again after finishing the clearance.

EN

55-EN

– 28 –

56-EN

 

 

Page 29