3 Push the SET button.
Installation Manual
Resetting the address |
Installation Manual |
•The address of one of the indoor units connected to the selected refrigerant line is indicated on the LCD display and the fan and louvers of the unit are activated.
At first, the current indoor unit address is displayed in SET DATA.
(No system address is indicated.)
| CODE No. |
SET DATA SETTING |
|
UNIT | No. |
R.C. | No. |
TEMP. | ON / OFF |
(Resetting to the factory |
default (address undecided)) |
Method 1
Clearing each address separately using a wired remote controller.
Set the system address, indoor unit address and group address to “0099” using a wired remote controller. (For the setting procedure, refer to the address setting procedures using the wired remote controller on the previous pages.)
Method 2
Clearing all the indoor unit addresses on a refrigerate line at
Header |
| Follower unit | |
unit |
| ||
U3 U4 | U3 U4 | ||
U1 U2 | U5 U6 | U1 U2 | U5 U6 |
Header unit
U3 U4
U1 | U2 |
| U5 | U6 |
|
|
|
|
|
Follower unit
U3 U4 | |
U1 U2 | U5 U6 |
|
|
|
|
|
|
|
| Central control | |||||
|
|
|
|
|
|
|
| controller | |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| U1 | U2 |
| |
Header |
|
|
|
|
| U3 | U4 |
| |||||
|
|
|
|
|
|
|
|
| |||||
unit |
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| U3 | U4 |
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
| U1 | U2 |
|
| U5 | U6 |
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| TIMER SET |
4 |
| TIME |
FILTER |
| |
| RESET TEST | SET CL |
8 |
|
|
Finish |
|
|
6
once from the outdoor unit.
1 Turn off the refrigerant line to reset to the factory default and set the header outdoor unit of the line as below.
1) Disconnect the relay connectors between the |
[U1, U2] and [U3, U4] terminals. |
U1 | U2 |
|
|
| U1 | U2 |
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
| A | B |
|
|
| A | B |
| ||
Remote |
| Remote | |||||||||
controller |
| controller |
U1 U2
A B
Remote controller
U1 U2
A B
U1 U2
A B
Remote controller
5, 7 |
Press to finish setting.
(Leave them as they are if they have already |
been disconnected.) |
2) Turn on dip switch 2 of SW30 on the interface |
Indoor units to have their addresses initialized
4 Push the TIME / buttons repeatedly to change the value of the indoor unit address in SET DATA.
Change the value in SET DATA to that of a new address.
5 Push the SET button to confirm the new address on SET DATA.
6 Push the button (left side of the button) repeatedly to select another address to change. Each time you push the button, the indoor unit numbers in a refrigerant line are indicated one after another. Only the fan and louvers of the selected indoor unit are activated.
Repeat steps 4 to 6 to change the indoor unit addresses so as to make each of them unique.
7 Push the SET button.
(All the segments on the LCD display light up.)
8 Push the TEST button to finish the procedure.
P.C. board of the header outdoor unit if the |
switch is OFF. |
(Leave it as it is if it has already been set to |
ON.) |
2 Turn on the indoor and outdoor units of the refrigerant line for which you want to initialize the addresses. About one minute after turning on the power, confirm that the
SW01 | SW02 | SW03 | SW04 | Clearable addresses |
2 | 1 | 2 | Confirm that the | System/indoor unit/group address |
“A.d.buS” and turn SW04 ON for more than five | ||||
|
|
| seconds. |
|
2 | 2 | 2 | Confirm that the | Central control address |
“A.d.nEt” and turn SW04 ON for more than five | ||||
|
|
| seconds. |
|
3 Confirm that the
4 After a time “U.1.L08” appears on the
If the
NOTE
Take care to carry out the procedure above correctly; otherwise, addresses in other refrigerate lines may also be cleared.
5 Set the addresses again after finishing the clearance.
EN
– 28 – | ||
|
|