| Installation Manual | ||
|
|
| |
| Check code |
| |
|
| ||
Indication on | Check code name | ||
| Auxiliary code |
| |
| 01: Compressor 1 |
| |
P07 | 02: Compressor 2 | Heat sink overheat error | |
| 03: Compressor 3 |
| |
P10 | Detected indoor unit address | Indoor overflow error | |
P13 | — | Outdoor unit flow back error detected | |
|
|
| |
P15 | 01: TS condition | Gas leak detection | |
02: TD condition | |||
|
| ||
P17 | — | Discharge temperature TD2 error | |
|
|
| |
P18 | — | Discharge temperature TD3 error | |
|
|
| |
P19 | Detected outdoor unit number | ||
P20 | — | ||
|
|
| |
| 0 *: IGBT circuit |
| |
| 1 *: Position detection circuit error | Outdoor fan IPDU error | |
| 3 *: Motor lock error | ||
P22 | 4 *: Motor current detected | (NOTE) | |
C *: TH sensor error | |||
| |||
| D *: TH sensor error | Ignore | |
| E *: Inverter DC voltage error |
| |
| (outdoor unit’s fan) |
| |
| 01: Compressor 1 |
| |
P26 | 02: Compressor 2 | ||
| 03: Compressor 3 |
| |
| 01: Compressor 1 |
| |
P29 | 02: Compressor 2 | Compressor position detecting circuit error | |
| 03: Compressor 3 |
|
*1PDU number information 01:Compressor 1 02:Compressor 2 03:Compressors 1 and 2 04:Compressor 3 05:Compressors 1 and 3 06:Compressors 2 and 3 07:Compressors 1, 2 and 3 08:Fan 09:Compressor 1 and fan 0A:Compressor 2 and fan 0B:Compressors 1, 2 and fan 0C:Compressor 3 and fan 0D:Compressors 1, 3 and fan 0E:Compressors 2, 3 and fan 0F:Compressors 1, 2, 3, and fan
Installation Manual |
12MACHINE CARD AND LOGBOOK
Machine card
After test run, fill the items on the machine card and paste the card on an accessible place on the product securely before delivery to the customer.
Describe the following items on the machine card:
name, address and telephone number of the installer, his service department, the service department of the party concerned or at any addresses and telephone numbers of fire department, police, hospitals and burn centres;
Logbook
Update the log periodically after maintenance as defined in
Describe the following items on the logbook:
1.details of the maintenance and repair works;
2.quantities, kind of (new, reused, recycled) refrigerant which have been charged on each occasion, the quantities of refrigerant which have been transferred from the system on each occasion (see also
3.if there is an analysis of a reused refrigerant, the results shall be kept in the logbook;
4.source of the reused refrigerant;
5.changes and replacements of components of the system;
6.result of all periodic routine tests;
7.significant periods of
EN
| – 32 – |
|
|
|