– 5 – |
Installation Manual |
4 SELECTION OF INSTALLATION PLACE
Upon customer’s approval, install the air conditioner in a place which satisfies the following conditions:
•Place where it can be installed horizontally.
•Place which can reserve a sufficient service space for safe maintenance or checks.
•Place where there is no problem even if the drained water overflows.
Avoid the following places:
•Salty places (seaside area) or places with much gas sulfide (hot spring area) (If selecting such a place, special maintenance is required.)
•Places where oil (including machine oil), steam, oil smoke or corrosive gas is generated.
•Places where an organic solvent is used.
•Chemical plants with a cooling system using liquid carbon dioxide.
•Places where a device generating high frequency (inverter,
•Places where discharged air from the outdoor unit blows against the windows of a neighbour's house.
•Places unable to bear the weight of the unit.
•Places with poor ventilation.
Installation Manual |
Installation space
Leave space necessary for running, installation and servicing.
Air discharge
Air intake
Air intake
Air intake
Air intake
Installation/servicing surface
Square hole for handling
Outdoor unit top view
500mm or more |
|
|
(Rear side) |
|
|
10mm or more |
|
|
500mm or more |
|
|
(Front side) | 20mm or more | 20mm or more |
10mm or more
NOTE
•If there is an obstacle above the outdoor unit, leave a space of 2000mm or more to the top end of the outdoor unit.