Installation Manual |
Be sure to keep the rule of below tables about size and length of communication wiring.
Central |
|
|
|
|
|
| |||
control |
|
|
|
|
|
| |||
controller |
| Super modular multi system |
|
| |||||
|
|
|
|
|
|
| |||
| U1 | U2 |
|
|
|
|
|
|
|
| U3 | U4 |
|
|
|
|
|
| |
|
|
|
|
| L4 |
|
| Follower | |
|
|
|
|
|
|
|
| ||
|
|
| Header | Header | Follower | Follower | Follower | Header | |
|
|
| unit | unit | unit | unit | unit | unit | unit |
Outdoor unit | U3 U4 | U3 U4 | U3 U4 |
| U3 U4 | U3 U4 | U3 U4 |
| U3 U4 | |||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
| U1 U2 | U5 U6 | U1 U2 | U5 U6 | U1 U2 | U5 U6 | U1 U2 | U5 U6 | U1 U2 | U5 U6 | U1 U2 | U5 U6 | U1 U2 | U5 U6 | ||
L1 |
|
|
|
|
|
|
| L5 |
|
|
|
|
| |||
|
|
|
|
| L2 |
|
|
|
|
|
|
|
| L3 |
| |
Indoor unit | U1 U2 |
| U1 U2 |
| U1 U2 |
| U1 U2 | U1 U2 |
|
| U1 U2 |
|
| U1 U2 | U1 U2 | |
| A B | A B | A B |
|
| A B | A B |
|
| A B |
| A B | A B | |||
|
|
|
|
|
|
|
|
|
|
| L7 |
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
| L6 |
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Remote controller | Remote controller |
Remote controller
Wiring | |
Type | Shield wire |
|
|
Size/Length | 1.25 mm2: Up to 1000 m/2.0 mm2: Up to 2000 m (*1) |
(*1): Total length of Communication wiring length for all refrigerant circuits (L1 + L2 + L3 + L4)
Wiring | |
|
|
Type | Shield wire |
Size/Length | 1.25 mm2 to 2.0 mm2/Up to 100 m (L5) |
Table-3 Remote controller wiring (L6, L7)
Wire | |
|
|
Size | 0.5 mm2 to 2.0 mm2 |
| • Up to 500 m (L6 + L7) |
Length | • Up 400 m in case of wireless remote controller in group control. |
| • Up to 200 m total length of communication wiring between indoor units (L6) |
Installation Manual |
◆Group control through a Remote Controller
Group control of multiple indoor units (8 units) through a single remote controller switch
Indoor unit |
|
|
|
|
| |
No.1 |
| No.2 | No.3 | No.4 | No.7 | No.8 |
A B |
| A B | A B | A B | A B | A B |
Remote controller | (A.B) |
|
|
|
|
|
|
|
|
|
|
|
Connection of power wires and communication wires
Remove knockouts on the piping/wiring panel on the front of the unit and the panel on the bottom to get the power and communication wires through the holes.
| Piping/wiring panel |
Knockout for the |
|
communication wire | Knockout for the power |
Knockout for the power | supply wire |
wire |
|
NOTE
Be sure to separate the power wire and communication wires.
EN