Toshiba MMY-MAP0804HT8ZG-E Group control through a Remote Controller, SMMS-i, Installation Manual

Models: MMY-MAP0804HT8-E MMY-MAP1604HT8Z-E MMY-MAP1404HT8-E MMY-MAP0804HT8Z-E MMY-MAP1204HT8Z-E MMY-MAP1204HT8ZG-E MMY-MAP1404HT8Z-E MMY-MAP1004HT8-E MMY-MAP0804HT8ZG-E MMY-MAP1404HT8ZG-E MMY-MAP1004HT8Z-E MMY-MAP1204HT8-E MMY-MAP1004HT8ZG-E MMY-MAP1604HT8-E MMY-MAP1604HT8ZG-E

1 34
Download 34 pages 21.99 Kb
Page 21
Image 21
Table-3 Remote controller wiring (L6, L7)

SMMS-i

Installation Manual

Be sure to keep the rule of below tables about size and length of communication wiring.

Central

 

 

 

 

 

 

control

 

 

 

 

 

 

controller

 

Super modular multi system

 

 

 

 

 

 

 

 

 

 

U1

U2

 

 

 

 

 

 

 

 

U3

U4

 

 

 

 

Table-1

 

 

 

 

 

 

 

L4

 

 

Follower

 

 

 

 

 

 

 

 

 

 

 

Header

Header

Follower

Follower

Follower

Header

 

 

 

unit

unit

unit

unit

unit

unit

unit

Outdoor unit

U3 U4

U3 U4

U3 U4

 

U3 U4

U3 U4

U3 U4

 

U3 U4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

U1 U2

U5 U6

U1 U2

U5 U6

U1 U2

U5 U6

U1 U2

U5 U6

U1 U2

U5 U6

U1 U2

U5 U6

U1 U2

U5 U6

L1

 

 

 

 

 

 

 

L5

 

 

Table-1

 

 

Table-2

 

 

 

 

 

 

L2

 

 

 

 

 

 

 

 

L3

 

Indoor unit

U1 U2

 

U1 U2

 

U1 U2

 

U1 U2

U1 U2

 

 

U1 U2

 

 

U1 U2

U1 U2

 

A B

A B

A B

 

 

A B

A B

 

 

A B

 

A B

A B

 

 

Table-3

 

 

 

 

 

 

 

 

 

L7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

L6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Remote controller

Remote controller

Remote controller

Table-1 Communication wiring between indoor and outdoor units (L1, L2, L3), Central control wiring (L4)

Wiring

2-core, non-polarity

Type

Shield wire

 

 

Size/Length

1.25 mm2: Up to 1000 m/2.0 mm2: Up to 2000 m (*1)

(*1): Total length of Communication wiring length for all refrigerant circuits (L1 + L2 + L3 + L4)

Table-2 Communication wiring between outdoor units (L5)

Wiring

2-core, non-polarity

 

 

Type

Shield wire

Size/Length

1.25 mm2 to 2.0 mm2/Up to 100 m (L5)

Table-3 Remote controller wiring (L6, L7)

Wire

2-core, non-polarity

 

 

Size

0.5 mm2 to 2.0 mm2

 

• Up to 500 m (L6 + L7)

Length

• Up 400 m in case of wireless remote controller in group control.

 

• Up to 200 m total length of communication wiring between indoor units (L6)

SMMS-i

Installation Manual

Group control through a Remote Controller

Group control of multiple indoor units (8 units) through a single remote controller switch

Indoor unit

 

 

 

 

 

No.1

 

No.2

No.3

No.4

No.7

No.8

A B

 

A B

A B

A B

A B

A B

Remote controller

(A.B)

 

 

 

 

 

 

 

 

 

 

 

„Connection of power wires and communication wires

Remove knockouts on the piping/wiring panel on the front of the unit and the panel on the bottom to get the power and communication wires through the holes.

 

Piping/wiring panel

Knockout for the

 

communication wire

Knockout for the power

Knockout for the power

supply wire

wire

 

NOTE

Be sure to separate the power wire and communication wires.

EN

39-EN