No. Piping parts | Name | Selection of pipe size |
|
| Remarks | |
|
|
|
|
|
|
|
|
| Connecting pipe size of indoor unit |
|
|
|
|
|
|
|
|
|
|
|
|
| Capacity rank | Gas side | Liquid | ||
|
| side | ||||
|
|
|
|
|
– 13 – |
|
Installation Manual |
Allowable length of refrigerant pipes and allowable height difference between units
Branching section |
| 007 to 012 type | 15m or less real length | Ø9.5 | Ø6.4 |
Indoor unit |
|
|
| ||
|
|
| |||
(5) È |
| Real length exceeds 15m | Ø12.7 | Ø6.4 | |
connecting pipe |
| ||||
Indoor unit |
| 015 to 018 type | Ø12.7 | Ø6.4 | |
|
| ||||
|
|
|
|
| |
|
| 024 to 056 type | Ø15.9 | Ø9.5 | |
|
|
|
|
| |
|
| 072 to 096 type | Ø22.2 | Ø12.7 |
Selection of branching section
|
|
|
| Total capacity code of indoor units |
| Model name |
|
| |||||
|
|
|
| Equivalent to HP |
| Equivalent to |
|
|
| ||||
|
|
|
|
|
| capacity |
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
| ||
(6) | Branching section |
|
| Below 6.4 |
|
| Below 18.0 |
|
|
| |||
branching joint |
|
|
|
|
|
|
| ||||||
|
|
| 6.4 to below 14.2 |
| 18.0 to below 40.0 |
|
|
| |||||
|
|
| branching joint | 14.2 to below 25.2 |
| 40.0 to below 70.5 |
|
|
| ||||
|
|
|
|
|
|
|
| ||||||
|
|
|
|
| 25.2 or more |
|
| 70.5 or more |
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Selection of branching section (Branching header) |
|
|
|
| |||||||
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
| Total capacity code of indoor units |
| Model name |
| ||||||
|
|
|
| Equivalent to HP |
| Equivalent to |
|
| |||||
|
|
|
|
| capacity |
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
| For 4 |
| Below 14.2 |
| Below 40.0 |
|
| |||
|
|
| *2 | branches | 14.2 to below 25.2 | 40.0 to below 70.5 |
|
| |||||
|
|
|
|
|
|
| |||||||
(7) | Branching section | Branching header | Branching header | For 8 |
| Below 14.2 |
| Below 40.0 |
|
| |||
|
|
|
| branches | 14.2 to below 25.2 | 40.0 to below 70.5 |
|
| |||||
|
|
|
|
|
|
|
| ||||||
|
|
|
|
|
|
|
|
| |||||
|
| *2: Up to a total of 6.0 maximum equivalent to HP capacity codes is connectable to one line | |||||||||||
|
|
| after branching of header. When the total capacity codes of all outdoor units are 12 to below | ||||||||||
|
|
| 26 (equivalent to HP) and you use a branching header for the first branching section, use |
a
Outdoor unit connection piping kit (For linking of outdoor units)
|
|
|
| Total capacity code of outdoor units*3 | Model name | |
|
|
|
| Equivalent to HP | Equivalent to | |
|
| Outdoor unit |
| capacity |
| |
|
|
|
|
| ||
(8) | Branching section | connection piping | Outdoor unit | Below 26.0 | Below 73.0 | |
kit (For linking of | ||||||
|
| outdoor units) | connection piping |
|
|
|
|
| kit (For linking of | 26.0 or more | Above 73.0 | ||
|
|
| outdoor units) | |||
|
|
|
|
|
| |
|
|
| *3: Downstream side when regarding the main piping as the start point |
|
Height difference between outdoor units
H3 ≤ 5 m
Height difference between outdoor and indoor units:
H1 ≤ 70 m
D
Follower unit
| Outdoor unit |
|
| |
| A | B | C | pipes |
| unit | unit | unit | |
| Header Follower | Follower | connectingunit | |
|
|
| Ld | |
|
|
|
| |
| La | Lb | Lc | Outdoor |
|
|
|
| |
| LA | LB |
|
|
L1 | Outdoor unit connection piping kit |
| ||
(For linking of outdoor units) |
| |||
piping |
| |||
The longest piping between outdoor units: | ||||
Main | L0 ≤ 25 m |
|
| |
|
|
|
|
|
|
| Branching header |
|
| |
| Indoor unit connecting |
| ||||
| L7 | joint |
| |||
First branching | pipe |
|
| |||
|
|
|
| |||
section |
| Indoor unit |
|
|
|
|
|
| a | b | c | d | e |
L3 |
| The longest piping length: L ≤ 235 m |
| |||
| The longest piping length from the first branch: Li ≤ 90 m |
| ||||
|
| L5 | L6 |
|
| |
| branching joint | L4 |
|
| ||
|
|
|
| |||
|
|
|
|
| ||
| f | g |
| h | i | j |
|
|
|
|
|
| |
| Indoor unit |
|
|
|
|
(j)
Height difference between indoor units: H2 ≤ 40 m