10TEST RUN

57-EN

SMMS-i

10TEST RUN

„Before test run

Confirm that the valve of the refrigerate pipe of the outdoor unit is OPEN.

Before turning on the power, confirm that the resistance between the terminal block of power supply and the earth is more than 1MΩ using a 500V megohmmeter.

Do not run the unit if it is less than 1MΩ.

„Before test runCAUTION

Turn on the power and turn on the case heater of the compressor.

To save the compressor when it is activated, leave the power on for more than 12 hours.

„Methods of test run

When executing a test run using a

remote controller

Operate the system normally to check the running condition using the wired remote controller. Follow the instructions in the supplied owner’s manual when operating the unit.

If you use a wireless remote controller for operations, follow the instructions in the installation manual supplied with the indoor unit.

To execute a test run forcibly under the condition that the thermostat automatically turns the unit off due to the indoor temperature, follow the procedure below.

The forcible test run will automatically stop after 60 minutes to prevent continuous forcible running and return to normal running.

„Methods of test runCAUTION

Do not use forcible running except for a test run as it overloads the unit.

 

 

Installation Manual

TEMP.

ON / OFF

2, 4

 

 

TIMER SET

 

3

TIME

 

FILTER

 

 

RESET TEST SET CL

 

 

 

1, 5

 

 

 

1

Push and hold the TEST button for more than 4

 

seconds. TEST appears on the LCD display

 

and the unit enters the trial mode.

 

(TEST is indicated on the LCD display during

 

the test run.)

 

 

 

 

 

 

 

 

 

 

 

 

 

TEST

 

 

2

 

 

 

 

 

Push the

ON / OFF button.

3

Push the

MODE button to switch the running

mode to COOL or HEAT.

NOTE

Do not run the unit in any mode other than COOL or HEAT.

You cannot change the temperature setting during the test run.

Errors are detected as usual.

 

 

 

 

 

 

 

 

TEST

 

4

 

 

 

 

Push the ON / OFF button to stop running

 

after finishing the trial run.

 

The indication on the LCD display returns to

5

the status of procedure 1.

Push the TEST button to exit the trial mode.

 

(TEST disappears on the LCD display and

 

the status changes to normal stopped

 

mode.)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

– 29 –

SMMS-i

When executing a test run using the interface P.C. board on the

outdoor unit

You can execute a test run by operating switches on the interface P.C. board of the header outdoor unit.

“Individual trial”, which tests each indoor unit separately, and “corrective trial”, which tests all the indoor units connected, are available.

<Individual test operation>

Starting operation

1 Set the running mode to “COOL” or “HEAT” on the remote controller of the indoor unit to be tested.

(The unit will run in the current mode unless you set the mode otherwise.)

7-segment display

[A][B]

[U1]

[

]

2 Set the rotary switches on the interface P.C. board of the header outdoor unit: SW01 to [16], SW02 and SW03 to the address of the indoor unit to be tested.

SW02

SW03

Indoor unit address

 

 

 

 

1 to 16

1

1 to 16

Set number of SW02

 

 

 

 

1 to 16

2

17 to 32

Set number of SW02 + 16

 

 

 

 

1 to 16

3

33 to 48

Set number of SW02 + 32

1 to 16

4

49 to 64

Set number of SW02 + 48

 

 

 

 

7-segment display

[A][B]

[

]

[

]

￿

Address display of the corresponding indoor unit

3 Push and hold SW04 for more than 10 seconds.

7-segment display

[A][B]

[

]

[

]

 

￿

 

￿

Address display of the

[FF] is displayed for 5

corresponding indoor unit

seconds.

 

58-EN

Installation Manual

NOTE

The running mode follows the mode setting on the remote controller of the target indoor unit.

You cannot change the temperature setting during the test run.

Errors are detected as usual.

The unit does not perform test run for 3 minutes after turning the power on or stopping running.

Finishing operation

1 Set the rotary switches on the interface P.C. board of the header unit back: SW01 to [1], SW02 to [1] and SW03 to [1].

7-segment display

[A][B]

[U1]

[

]