![– 21 –](/images/new-backgrounds/35001/3500143x1.webp)
– 21 – |
Installation Manual |
Power supply terminal
block
Cord clamps
Communication terminal block
Power supply wires
Cord clamp
Earth screw
Communication wires
◆Power supply wire connection
1.Insert the power supply wire through the cutout on the side of the electric parts box and connect the power supply wire to the power supply terminal block and the earth line to the earth screw. After that, fix the power supply wire with the 2 cord clamps.
2.Be sure to use
Also, apply insulating sleeves to the crimping parts. Use a driver of appropriate size to fix the terminal screws.
L1 L2 L3 N
L1 L2 L3 N
10mm or more |
|
Earth line | Power supply wire |
|
| Installation Manual | ||
Screw size and tightening torque |
|
|
|
|
|
|
|
| Screw size | Tightening torque |
|
| (N•m) |
| |
|
|
| |
Power supply terminal | M6 | 2.5 to 3.0 |
|
|
|
|
|
Earth screw | M8 | 5.5 to 6.6 |
|
|
|
|
|
◆Communication wire connection
Get the communication wire through the cutout on the side of the electric parts box and connect it to the communication wire terminals, then fix it with the communication cable clamp.
U1 | U2 | U3 | U4 | U5 | U6 |
|
|
|
TO |
| TO |
| TO |
|
|
|
|
| CENTRAL |
|
|
|
| |||
INDOOR | OUTDOOR |
|
|
| ||||
CONTROL |
|
|
| |||||
UNIT | LER | UNIT |
|
|
| |||
|
|
|
|
|
|
| ||
|
|
|
|
|
| U5, U6: Communication wiring between outdoor units | ||
|
|
|
|
|
| U3, U4: Central control device | ||
|
|
|
|
|
| U1, U2: Communication wiring between Indoor/Outdoor unit | ||
Screw size and tightening torque |
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
| Screw size | Tightening torque |
| |
|
|
|
|
| (N•m) |
| ||
|
|
|
|
|
|
|
| |
Communication wire terminal |
|
|
| M3.5 |
| 0.80 to 0.96 |
| |
|
|
|
|
|
|
|
|
|