Toshiba MMY-MAP1204HT8Z-E, MMY-MAP1604HT8ZG-E After the indication, When the flashing stops and

Models: MMY-MAP0804HT8-E MMY-MAP1604HT8Z-E MMY-MAP1404HT8-E MMY-MAP0804HT8Z-E MMY-MAP1204HT8Z-E MMY-MAP1204HT8ZG-E MMY-MAP1404HT8Z-E MMY-MAP1004HT8-E MMY-MAP0804HT8ZG-E MMY-MAP1404HT8ZG-E MMY-MAP1004HT8Z-E MMY-MAP1204HT8-E MMY-MAP1004HT8ZG-E MMY-MAP1604HT8-E MMY-MAP1604HT8ZG-E

1 34
Download 34 pages 21.99 Kb
Page 25
Image 25
10Set the central control address.
complete.
7 Repeat steps 4 to 6 for other refrigerant lines.
8 After completing address setting of all systems, turn off dip switch 2 of SW30 on the interface P.C. boards of all the header outdoor units connected to the same central control, except the unit that has the lowest address.
(For unifying the termination of the wiring for the central control of indoor and outdoor units)

SMMS-i

 

 

 

 

 

 

Installation Manual

 

 

 

 

 

 

 

 

 

Line (system) address

 

 

SW13

 

 

 

SW14

 

 

 

 

 

 

 

 

 

1

2

3

4

1

2

3

4

 

26

{

{

{

27

{

{

{

 

 

 

 

 

 

 

 

 

28

{

{

{

{

“–”: not used for system address setting (Do not change their positions.)

2 Be sure to disconnect the relay connectors between the [U1U2] and [U3U4] terminals on all the header outdoor units that will be connected to the central control. (Factory default: disconnected)

2

U1

U2

U3

U4

U5

U6

 

 

TO

 

TO

 

TO

 

 

 

CENTRAL

 

 

INDOOR

OUTDOOR

 

CONTROL

 

UNIT

UNIT

 

LER

 

 

 

 

 

3

Turn on indoor units first, and then turn on outdoor units.

4

About 1 minute after turning the power on, confirm that the 7-segment display on the interface

 

P.C. board of the header outdoor unit indicates

 

U. 1. L08 (U. 1. flash)

.

5

Press SW 15 to start the automatic address setting.

6

(It may take up to 10 minutes (normally about 5 minutes) to complete one line’s setting.)

The 7-segment display indicates

 

 

 

 

.

 

Auto 1 Auto 2 Auto 3

 

After the indication,

 

 

starts flashing on the display.

 

U. 1. - - - (U. 1. flash)

 

When the flashing stops and

 

 

 

, remains lit on the display, the setting is

 

 

U. 1. - - - (U. 1. light)

 

SMMS-i

Installation Manual

9 Connect the relay connectors between the [U1, U2] and [U3, U4] terminals of the header outdoor unit of each refrigerant line.

9

U1

 

U2

U3

 

U4

U5

 

U6

TO

 

 

TO

TO

 

 

CENTRAL

 

INDOOR

OUTDOOR

CONTROL

UNIT

LER

UNIT

 

 

 

 

 

 

10Set the central control address.

(For the setting of the central control address, refer to the installation manuals of the central control devices.)

Header unit interface P.C. board

 

 

SW15

 

 

SW04 SW05

 

7-segment

D600 D601 D602 D603 D604

 

display

 

SW13

SW14

SW01 SW02 SW03

SW30

1 2

EN

47-EN

– 24 –

48-EN

 

 

Page 25
Image 25
Toshiba MMY-MAP1204HT8Z-E After the indication, When the flashing stops and, 10Set the central control address