Toshiba MMY-MAP1004HT8Z-E Electric Wiring, „Power supply specifications, Pipe holding bracket

Models: MMY-MAP0804HT8-E MMY-MAP1604HT8Z-E MMY-MAP1404HT8-E MMY-MAP0804HT8Z-E MMY-MAP1204HT8Z-E MMY-MAP1204HT8ZG-E MMY-MAP1404HT8Z-E MMY-MAP1004HT8-E MMY-MAP0804HT8ZG-E MMY-MAP1404HT8ZG-E MMY-MAP1004HT8Z-E MMY-MAP1204HT8-E MMY-MAP1004HT8ZG-E MMY-MAP1604HT8-E MMY-MAP1604HT8ZG-E

1 34
Download 34 pages 21.99 Kb
Page 19
Image 19
SMMS-i

SMMS-i

When using the piping cover

Piping/wiring panel

Drawing-out sideward

Close the opening with the pipe cover.

Drawing-out

frontwardDrawing-out downward

Pipe holding bracket

Attach pipe holding brackets following the table below.

Diameter of pipe (mm)

Interval

Ø15.9 - Ø19.1

2m

 

 

Ø22.2 - Ø41.3

3m

Installation Manual

When not using the piping cover

Piping/wiring panel

Drawing-out sideward

Fill silicon or putty into the periphery of the pipes.

Drawing-out

frontwardDrawing-out downward

SMMS-i

Installation Manual

8 ELECTRIC WIRING

◆Pipe holding bracketWARNING

The appliance shall be installed in accordance with national wiring regulations.

Capacity shortages of the power circuit or an incomplete installation may cause an electric shock or fire.

When not using the piping coverCAUTION

Perform wiring of power supply complying with the rules and regulations of the local electric company.

Do not connect 380V - 415V power to the terminal blocks for control cables (U1, U2, U3, U4, U5, U6); otherwise, the unit may break down.

Be sure that electric wiring does not come into contact with high-temperature parts of piping; otherwise, the coating of cables may melt and cause an accident.

After connecting wires to the terminal block, take off the traps and fix the wires with cord clamps.

Follow the same structure for both the control wiring and refrigerate piping.

Do not conduct power to indoor units until vacuuming of the refrigerant pipes has finished.

For the wiring of power to indoor units and that between indoor and outdoor units, follow the instructions in the installation manual of each indoor unit.

„Power supply specifications

Do not bridge the power between outdoor units through the equipped terminal blocks (L1, L2, L3, N).

Power supply for outdoor units

NO GOOD

Power wiring selection

Standard model

MCA: Minimum Circuit Amps

MOCP: Maximum Overcurrent Protection (Amps)

Model

Power Supply

 

MCA

MOCP

 

 

 

 

 

(A)

(A)

 

 

Phase and frequency

 

Nominal Voltage

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MMY-MAP0804*

 

 

 

23.5

32

 

 

MMY-MAP1004*

 

 

 

25.5

32

 

 

MMY-MAP1204*

3N~ 50Hz

 

380-400-415V

28.5

40

 

 

MMY-MAP1404*

 

 

 

33.2

40

 

 

MMY-MAP1604*

 

 

 

36.5

50

 

 

MMY-AP1814*

 

 

 

49.0

63

 

 

MMY-AP2014*

 

 

 

51.0

63

 

 

MMY-AP2214*

 

 

 

54.0

63

 

 

MMY-AP2414*

3N~ 50Hz

 

380-400-415V

57.0

63

 

 

MMY-AP2614*

 

62.0

80

 

 

 

 

 

 

 

MMY-AP2814*

 

 

 

65.0

80

 

EN

MMY-AP3014*

 

 

 

69.7

80

 

MMY-AP3214*

 

 

 

73.0

100

 

 

 

 

 

 

 

 

 

 

35-EN

– 18 –

36-EN

 

 

Page 19
Image 19