| Installation Manual |
|
|
|
|
|
|
|
| Installation Manual | |||
Header | Follower | Follower | Follower |
|
|
|
|
|
| No. | Piping parts | Name |
|
|
| Selection of pipe size |
| Remarks | ||
|
|
|
|
|
|
|
|
| Connecting pipe size of outdoor unit |
|
|
| ||||||||
unit A | unit B | unit C | unit D |
|
|
|
|
|
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
|
| Type |
|
| Gas side |
| Liquid side |
| |
Outdoor unit |
|
|
|
|
|
|
|
|
|
| Outdoor unit |
| MAP080 |
|
| Ø22.2 |
| Ø12.7 | Same as connecting | |
|
|
|
|
|
|
|
|
| (1) | È | Outdoor unit | MAP100 |
|
| Ø22.2 |
| Ø12.7 | |||
|
|
|
|
|
|
|
|
|
| Outdoor unit |
|
|
| pipe size of the | ||||||
|
|
|
|
|
|
|
|
|
| connecting pipe | MAP120 |
|
| Ø28.6 |
| Ø12.7 | ||||
|
|
|
|
|
|
|
|
|
|
| connection piping |
|
|
|
| outdoor unit. | ||||
|
|
|
|
|
|
|
|
|
|
| kit |
| MAP140 |
|
| Ø28.6 |
| Ø15.9 |
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
(1) |
| (1) | (1) | (2) Balance pipes Ø9.5 |
|
|
|
|
|
|
| MAP160 |
|
| Ø28.6 |
| Ø15.9 |
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||
(8) |
|
|
|
|
|
|
|
|
|
|
|
| Pipe size for connecting piping between outdoor units |
| ||||||
|
|
|
| (1) Outdoor unit connecting pipes |
|
|
|
|
|
| ||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
(8) | (8) |
|
|
|
|
|
|
|
|
|
| Total capacity codes of |
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
| outdoor units at the |
|
|
|
| ||||||
|
|
|
|
|
|
|
|
|
|
|
| Gas | Liquid | Balanc |
| |||||
(2) | (2) |
|
|
|
|
|
|
|
|
|
| downstream side |
| |||||||
|
|
|
|
|
|
|
|
|
| Equivalent to | Equivalent to | side | side | e pipe | Pipe size differs based | |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||
(3) Main |
|
|
|
|
|
|
|
|
|
| Between Outdoor | Main connecting | HP |
|
| capacity |
|
|
| on the total capacity |
|
|
|
|
|
|
|
|
| (2) |
| 45.0 to below |
|
|
| code value of outdoor | |||||
piping | (8) Outdoor unit connection piping kit (For linking of outdoor units) |
|
| unit connection | piping between | 16 to below 22 | Ø28.6 | Ø15.9 |
| units at the | ||||||||||
|
|
|
| piping kits | outdoor units |
|
| 61.5 |
| |||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| downstream side. | |||
|
|
|
|
| (7) Branching header |
|
|
|
| 22 to below 26 |
| 61.5 to below | Ø34.9 | Ø19.1 |
| (See Table 2.) | ||||
(6) |
| (4) Branching pipe |
|
|
|
|
|
|
| 73.0 | Ø9.5 |
| ||||||||
|
|
|
|
|
|
|
|
|
|
|
| |||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
| 26 to below 36 |
| 73.0 to below | Ø34.9 | Ø19.1 |
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 101.0 |
|
| |||
First branch |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
| 36 or more | 101.0 or more | Ø41.3 | Ø22.2 |
|
| |||
|
|
|
|
|
|
| (6) |
|
|
|
|
| ||||||||
|
| (5) Indoor unit connecting pipe |
| (4) |
|
|
|
|
|
|
|
|
|
|
| |||||
branching joint |
|
|
|
|
|
|
|
| Size of main piping |
|
|
|
|
| ||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
| (4) |
| Indoor unit | (5) |
| (5) | (5) | (5) |
|
|
| Total capacity codes of all |
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||
|
|
|
|
|
|
|
|
|
|
|
|
| outdoor units |
| Gas | Liquid |
| |||
|
|
|
|
|
|
|
|
|
|
|
|
| Equivalent to |
| Equivalent to | side | side |
| ||
|
|
|
|
|
|
|
|
|
|
|
|
| HP |
|
| capacity |
|
|
|
|
|
|
|
|
| (6) |
|
| (6) |
|
| Outdoor unit |
| 8 to below 12 |
|
| 22.4 to below 33.5 | Ø22.2 | Ø12.7 |
| |
|
|
|
| (6) |
| (4) |
|
|
|
|
|
|
|
|
|
|
| |||
|
| (6) | (4) | (4) |
|
|
|
| connection piping |
| 12 to below 14 |
|
| 33.5 to below 38.4 | Ø28.6 | Ø12.7 | Pipe size differs based | |||
|
|
|
|
|
|
|
|
| (3) | kit of header unit | Main piping | 14 to below 22 |
|
| 38.4 to below 61.5 | Ø28.6 | Ø15.9 | on the capacity code | ||
|
|
|
|
|
|
|
|
|
|
|
| |||||||||
|
|
|
|
|
|
|
|
|
| È |
|
| of the outdoor unit. | |||||||
|
|
|
|
|
|
|
|
|
|
| First branching |
| 22 to below 36 |
|
| 61.5 to below | Ø34.9 | Ø19.1 | (See Table 2.) | |
|
|
| (5) |
| (5) | (5) |
| (5) | (5) |
| section |
|
|
| 101.0 |
|
| |||
|
|
|
|
|
|
|
|
|
|
| 101.1 to below |
|
|
| ||||||
|
|
|
|
|
|
|
|
|
|
|
|
| 36 to below 46 |
|
| Ø41.3 | Ø22.2 |
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 130.0 |
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
| Indoor unit |
|
|
|
|
|
|
|
| 46 or more |
|
| 130.0 or more | * Ø41.3 | Ø22.2 |
| ||
|
|
|
|
|
|
|
|
|
|
|
|
| * Maximum equivalent length of main pipe is 70m or less (The actual |
| ||||||
|
|
|
|
|
|
|
|
|
|
|
|
| length is 50m or less.). |
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
| Pipe size between branching sections *1 |
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
| Total capacity codes of indoor |
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
| units at downstream side |
| Gas | Liquid |
| |||
|
|
|
|
|
|
|
|
|
|
|
|
| Equivalent to HP | Equivalent to | side | side | Pipe size differs based | |||
|
|
|
|
|
|
|
|
|
|
|
|
| capacity |
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| on the total capacity | ||
|
|
|
|
|
|
|
|
|
|
|
|
| Below 2.4 |
|
| Below 6.6 |
| Ø12.7 | Ø9.5 | code value of indoor |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| units at the | ||||
|
|
|
|
|
|
|
|
|
|
| Branching section |
| 2.4 to below 6.4 |
| 6.6 to below 18.0 | Ø15.9 | Ø9.5 | downstream side. If | ||
|
|
|
|
|
|
|
|
|
| (4) | È | Branching pipe | 6.4 to below 12.2 |
| 18.0 to below 34.0 | Ø22.2 | Ø12.7 | the total value | ||
|
|
|
|
|
|
|
|
|
|
| exceeds the capacity | |||||||||
|
|
|
|
|
|
|
|
|
|
| Branching section |
| 12.2 to below 20.2 |
| 34.0 to below 56.5 | Ø28.6 | Ø15.9 | code of the outdoor | ||
|
|
|
|
|
|
|
|
|
|
|
|
|
| unit, apply the | ||||||
|
|
|
|
|
|
|
|
|
|
|
|
| 20.2 to below 35.2 |
| 56.5 to below 98.5 | Ø34.9 | Ø19.1 | capacity code of the | ||
|
|
|
|
|
|
|
|
|
|
|
|
|
| outdoor unit. (See | ||||||
|
|
|
|
|
|
|
|
|
|
|
|
| 35.2 or more |
|
| 98.5 ore more | Ø41.3 | Ø22.2 | Table 1 and 2.) | |
|
|
|
|
|
|
|
|
|
|
|
|
| *1: If exceeding the main pipe size, set the size to the same as the | EN | ||||||
|
|
|
|
|
|
|
|
|
|
|
|
| main pipe size. |
|
|
|
|
|
|