Installation
3.4.3 Wire Size
WARNING
ELECTROCUTION AND FIRE HAZARDS WITH IMPROPERLY INSTALLED AND GROUNDED FIELD WIRING!
Improperly installed and grounded field wiring poses FIRE & ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in the National Electrical Codes (NEC) and your local/state electrical codes. All field wiring MUST be performed by qualified personnel.
Failure to follow these requirements could result in death or serious injury.
NOTE!
Make all power connections with minimum 60 or 75°C/140 or 155°F rated copper wiring for installations in North America.
208 V AC
|
|
| Panel (TR200) Non | Maximum Field | Field Ground Wiring | Minimum Temperature | |
HP (KW) | UL Motor Current | Wiring Size Class B | Wire Rating "°C" Copper | ||||
Bypass & Bypass | Size Class B or C | ||||||
|
|
| or C | Conductor | |||
|
|
|
|
| |||
|
|
|
|
|
|
| |
7.5 | (5.5) | 24.2 |
| 8 AWG | 10 AWG | 60 | |
|
|
|
|
|
| ||
10 (7.5) | 30.8 | P2 | 8 AWG | 10 AWG | 60 | ||
|
|
|
|
|
|
| |
15 | (11) | 46.2 |
| 4 AWG | 10 AWG | 60 | |
|
|
|
|
|
|
| |
20 | (15) | 59.4 | P3 | 3 AWG | 10 AWG | 60 | |
|
|
|
|
|
|
| |
25 (18.5) | 74.8 | P3 - Non Bypass P4 - | 2 AWG | 8 AWG | 60 | ||
Bypass | |||||||
|
|
|
|
|
| ||
|
|
|
|
|
|
| |
30 | (22) | 88 | P4 | 2 AWG | 8 AWG | 60 | |
|
|
|
|
|
| ||
40 | (30) | 114 | 1/0 AWG | 6 AWG | 75 | ||
| |||||||
|
|
|
|
|
|
| |
50 | (37) | 143 | P5 | 3/0 AWG | 6 AWG | 75 | |
|
|
|
|
|
| ||
60 | (45) | 169 | 4/0 AWG | 6 AWG | 75 | ||
| |||||||
|
|
|
|
|
|
| |
|
|
|
| 230 VAC |
|
| |
|
|
|
|
|
|
| |
|
|
| Panel (TR200) Non | Maximum Field | Field Ground Wiring | Minimum Temperature | |
HP (KW) | UL Motor Current | Wiring Size Class B | Wire Rating "Degree C" | ||||
Bypass & Bypass | Size Class B or C | ||||||
|
|
| or C | Copper Conductor | |||
|
|
|
|
| |||
|
|
|
|
|
|
| |
7.5 | (5.5) | 22 |
| 10 AWG | 10 AWG | 60 | |
10 (7.5) | 28 | P2 | 8 AWG | 10 AWG | 60 | ||
15 | (11) | 42 |
| 6 AWG | 10 AWG | 60 | |
20 | (15) | 54 | P3 | 4 AWG | 10 AWG | 60 | |
|
|
|
|
|
| ||
25 (18.5) | 68 | 3AWG | 8 AWG | 60 | |||
| |||||||
|
|
|
|
|
|
| |
30 | (22) | 80 | P4 | 3 AWG | 8 AWG | 60 | |
|
|
|
|
|
| ||
40 | (30) | 104 |
| 1 AWG | 6 AWG | 75 | |
|
|
|
|
|
|
| |
50 | (37) | 130 | P5 | 2/0 AWG | 6 AWG | 75 | |
|
|
|
|
|
| ||
60 | (45) | 154 | 3/0 AWG | 6 AWG | 75 | ||
| |||||||
|
|
|
|
|
|
|
Table 3.9 Wire Size Chart, 208 and 230 V