3.4.3 Wire Size

Installation

3.4.3 Wire Size

Manual backgroundManual backgroundWARNING

ELECTROCUTION AND FIRE HAZARDS WITH IMPROPERLY INSTALLED AND GROUNDED FIELD WIRING!

Improperly installed and grounded field wiring poses FIRE & ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in the National Electrical Codes (NEC) and your local/state electrical codes. All field wiring MUST be performed by qualified personnel.

Failure to follow these requirements could result in death or serious injury.

NOTE!

Make all power connections with minimum 60 or 75°C/140 or 155°F rated copper wiring for installations in North America.

208 V AC

 

 

 

Panel (TR200) Non

Maximum Field

Field Ground Wiring

Minimum Temperature

HP (KW)

UL Motor Current

Wiring Size Class B

Wire Rating "°C" Copper

Bypass & Bypass

Size Class B or C

 

 

 

or C

Conductor

 

 

 

 

 

 

 

 

 

 

 

 

7.5

(5.5)

24.2

 

8 AWG

10 AWG

60

 

 

 

 

 

 

10 (7.5)

30.8

P2

8 AWG

10 AWG

60

 

 

 

 

 

 

 

15

(11)

46.2

 

4 AWG

10 AWG

60

 

 

 

 

 

 

 

20

(15)

59.4

P3

3 AWG

10 AWG

60

 

 

 

 

 

 

 

25 (18.5)

74.8

P3 - Non Bypass P4 -

2 AWG

8 AWG

60

Bypass

 

 

 

 

 

 

 

 

 

 

 

 

 

30

(22)

88

P4

2 AWG

8 AWG

60

 

 

 

 

 

 

40

(30)

114

1/0 AWG

6 AWG

75

 

 

 

 

 

 

 

 

50

(37)

143

P5

3/0 AWG

6 AWG

75

 

 

 

 

 

 

60

(45)

169

4/0 AWG

6 AWG

75

 

 

 

 

 

 

 

 

 

 

 

 

230 VAC

 

 

 

 

 

 

 

 

 

 

 

 

Panel (TR200) Non

Maximum Field

Field Ground Wiring

Minimum Temperature

HP (KW)

UL Motor Current

Wiring Size Class B

Wire Rating "Degree C"

Bypass & Bypass

Size Class B or C

 

 

 

or C

Copper Conductor

 

 

 

 

 

 

 

 

 

 

 

 

7.5

(5.5)

22

 

10 AWG

10 AWG

60

10 (7.5)

28

P2

8 AWG

10 AWG

60

15

(11)

42

 

6 AWG

10 AWG

60

20

(15)

54

P3

4 AWG

10 AWG

60

 

 

 

 

 

 

25 (18.5)

68

3AWG

8 AWG

60

 

 

 

 

 

 

 

 

30

(22)

80

P4

3 AWG

8 AWG

60

 

 

 

 

 

 

40

(30)

104

 

1 AWG

6 AWG

75

 

 

 

 

 

 

 

50

(37)

130

P5

2/0 AWG

6 AWG

75

 

 

 

 

 

 

60

(45)

154

3/0 AWG

6 AWG

75

 

 

 

 

 

 

 

 

Table 3.9 Wire Size Chart, 208 and 230 V

BAS-SVX49A-EN

3-19