Trane TR200 Electronically Controlled B, Input Conn, Function, Type, 2 ECB Card Terminals

Models: TR200 Vertical Bypass/Non Bypass Panel

1 86
Download 86 pages 30.73 Kb
Page 56
Image 56
Input Conn.

Electronically Controlled B...

Input Conn.

Term.

Function

Type

 

 

 

 

 

1

Digital input for safety stop

User supplied dry contact

 

2

Common

User supplied dry contact

 

3

Factory use only

 

 

4

No function

 

 

5

Factory use only

 

 

 

 

 

X57

6

Factory use only

 

 

 

 

7

Factory use only

 

 

 

 

 

 

 

 

8

Digital input for remote bypass enable

User supplied dry contact

 

 

 

 

 

9

Digital input overrides system to Bypass Mode ignoring all

User supplied dry contact

 

 

other inputs and commands, except for safety stop on

 

 

 

terminal 1.

 

 

 

 

 

 

10

Digital input for remote overload reset

User supplied dry contact

 

 

 

 

Output Conn.

Term.

Function

 

 

 

 

 

 

1

Common for binary I/O

 

 

 

 

 

 

2

Common for binary I/O

 

 

 

 

 

 

3

No function

 

 

 

 

 

X59

4

No function

 

 

 

 

5

Digital output indicates panel is in Drive Mode.

24 VDC digital output

 

 

 

 

 

 

6

Digital output indicates panel is in Bypass Mode

24 VDC digital output

 

 

 

 

 

7

Common for binary I/O

 

 

8

Common for binary I/O

 

Relay Output

Term.

Function

 

 

1

N.O. contact for running in bypass or drive

Relay output for user

X56

2

N.O. contact for running in bypass or drive

Relay output for user

 

3-12

Factory use only

 

 

 

 

 

Table 6.2 ECB Card Terminals

6-4

BAS-SVX49A-EN

Page 56
Image 56
Trane TR200 specifications Electronically Controlled B, Input Conn, Function, Type, 2 ECB Card Terminals