Trane TR200, Vertical Bypass/Non Bypass Panel specifications Installation, V Ac, 5 Drive Fuses

Models: TR200 Vertical Bypass/Non Bypass Panel

1 86
Download 86 pages 30.73 Kb
Page 16
Image 16
230 V AC

Installation

230 V AC

HP (KW)

UL Motor

 

Panel (TR200) Non Bypass

Main Fuse (TR200)

Drive Fuse (TR200)

Transformer Fuse (TR200)

Current

 

 

& Bypass

Bussman

Bussman

Bussman

 

 

 

7.5 (5.5)

22

 

 

 

LPJ-35-SP

JJN-50

 

10 (7.5)

28

 

 

P2

LPJ-45-SP

JJN-50

 

15 (11)

42

 

 

 

LPJ-70-SP

JJN-60

 

20 (15)

54

 

 

P3

LPJ-90-SP

JJN-80

 

25 (18.5)

68

 

 

LPJ-100-SP

JJN-125

 

 

 

 

 

 

 

 

 

 

 

 

 

30 (22)

80

 

 

P4

LPJ-125-SP

JJN-125

 

 

 

 

 

 

 

 

40 (30)

104

LPJ-150-SP

JJN-150

 

 

 

 

 

 

 

 

 

 

 

 

 

50 (37)

130

 

 

P5

LPJ-200-SP

JJN-200

FNQ-R-1.25

 

 

 

 

 

 

 

60 (45)

154

LPJ-250-SP

JJN-250

FNQ-R-1.25

 

 

 

 

 

 

 

 

 

 

 

Table 3.3 Drive Fuses 230 V

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

460 V AC

 

 

 

 

 

 

 

 

 

 

HP (KW)

UL Motor

 

 

Panel (TR200) Non

Main Fuse (TR200)

Drive Fuse (TR200)

Transformer Fuse (TR200)

Current

 

 

Bypass & Bypass

Bussman

Bussman

Bussman

 

 

 

 

 

 

 

 

 

 

 

15 (11)

21

 

 

 

LPJ-35-SP

JJS-40

 

 

 

 

 

 

 

 

 

20 (15)

27

 

 

P2

LPJ-40-SP

JJS-40

 

 

 

 

 

 

 

 

 

25 (18.5)

34

 

 

 

LPJ-50-SP

JJS-50

 

 

 

 

 

 

 

 

 

30 (22)

40

 

 

 

LPJ-60-SP

JJS-60

 

 

 

 

 

 

 

 

 

40 (30)

52

 

 

P3

LPJ-80-SP

JJS-80

 

50 (37)

65

 

 

 

LPJ-100-SP

JJS-100

 

60 (45)

77

 

 

P4

LPJ-125-SP

JJS-125

 

75 (55)

96

 

 

LPJ-150-SP

JJS-150

 

 

 

 

 

100 (75)

124

 

 

P5

LPJ-200-SP

JJS-200

FNQ-R-0.60

125 (90)

156

 

 

LPJ-250-SP

JJS-250

FNQ-R-0.60

 

 

 

Table 3.4 Drive Fuses 460 V

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

600 V AC

 

 

 

 

 

 

 

 

 

 

HP (KW)

UL Motor

 

 

Panel (TR200) Non

Main Fuse (TR200)

Drive Fuse (TR200)

Transformer Fuse (TR200)

Current

 

 

Bypass & Bypass

Bussman

Bussman

Bussman

 

 

 

 

 

 

 

 

 

 

 

15 (11)

17

 

 

 

LPJ-30-SP

JJS-35

 

 

 

 

 

 

 

 

 

20 (15)

22

 

 

P2

LPJ-35-SP

JJS-35

 

 

 

 

 

 

 

 

 

25 (18.5)

27

 

 

 

LPJ-45-SP

JJS-45

 

 

 

 

 

 

 

 

 

30 (22)

32

 

 

 

LPJ-50-SP

JJS-50

 

 

 

 

 

 

 

 

 

40 (30)

41

 

 

P3

LPJ-60-SP

JJS-60

 

 

 

 

 

 

 

 

 

50 (37)

52

 

 

 

LPJ-80-SP

JJS-80

 

 

 

 

 

 

 

 

 

60 (45)

62

 

 

P4

LPJ-100-SP

JJS-100

 

 

 

 

 

 

 

 

75 (55)

77

 

 

LPJ-125-SP

JJS-125

 

 

 

 

 

 

 

 

 

 

 

 

 

100 (75)

99

 

 

P5

LPJ-150-SP

JJS-150

FNQ-R-0.50

 

 

 

 

 

 

 

125 (90)

125

 

 

LPJ-200-SP

JJS-175

FNQ-R-0.50

 

 

 

 

 

 

 

 

 

 

 

Table 3.5 Drive Fuses 600 V

3-2

BAS-SVX49A-EN

Page 16
Image 16
Trane TR200, Vertical Bypass/Non Bypass Panel specifications Installation, V Ac, 5 Drive Fuses