Trane Vertical Bypass/Non Bypass Panel Mode of Operation Select, Par. No, Selection, Function

Models: TR200 Vertical Bypass/Non Bypass Panel

1 86
Download 86 pages 30.73 Kb
Page 61
Image 61
Mode of Operation Select

Electronically Controlled Bypass (ECB) Opera- tion

Auto bypass mode: When in drive mode, auto bypass is a timed interval that allows a fault condition in the drive to activate running the motor in bypass without operator intervention.

Mode of Operation Select

Mode of operation is programmed through parameter group 31-** . See Table 6.4.

Par. No.

Selection

Function

31-00

Bypass Mode

Selects source of motor power.

 

 

(0) Drive (drive mode) (1) Bypass (bypass

 

 

mode)

 

 

 

31-01

Bypass Start Time Delay

Sets a delay time for starting in bypass that

 

 

allows for external actions to take place prior

 

 

to line starting the motor.

 

 

 

 

 

0-60 sec. (default value is 5 sec.)

 

 

 

31-02

Bypass Trip Time Delay

Setting a value other than 0 sec. enables

 

 

auto bypass. Bypass trip delay sets the delay

 

 

time before switching to bypass mode when

 

 

the drive has a fault.

 

 

 

 

 

0-300 sec. (default is 0 sec. = OFF)

 

 

 

31-03

Test Mode Activation

Setting enabled puts bypass in test mode.

 

 

See the manual for warnings and cautions.

 

 

 

 

 

(0) disabled (default value) (1) enabled

 

 

 

31-10

Bypass Status Word

Read-only display, which shows the bypass

 

 

status in hex. See the next table for details.

 

 

 

 

 

0, 216-1 (default value is 0)

 

 

 

31-11

Bypass Running Hours

Read only display which shows bypass

 

 

running hours.

 

 

 

Table 6.4 Bypass Parameter Functions

Bit

Description

 

 

0

Test Mode The Test Mode bit will be true when the ECB is in Test Mode.

 

 

1

Drive Mode The Drive Mode bit will be true when the ECB is in Drive Mode.

 

 

2

Automatic Bypass Mode The Automatic Bypass Mode bit will be true when the ECB is in Automatic Bypass Mode.

3

Bypass Mode The Bypass Mode bit will be true when the ECB is in Bypass Mode.

4

Reserved This bit is reserved for future use.

5

Motor Running from Bypass/Drive The Motor Running from Bypass/Drive Bit will be true when the motor is running from

 

either the drive or the bypass.

6

Overload Trip The Overload Trip Bit will be true when the ECB detects an overload trip.

 

 

7

M2 Contactor Fault The Contactor Fault Bit will be true when an M2 Contactor Fault is detected.

 

 

8

M3 Contactor Fault The Contactor Fault Bit will be true when an M3 Contactor Fault is detected.

 

 

9

External Interlock The External Interlock Bit will be true when an External Interlock fault is detected.

 

 

10

Manual Bypass Override The Manual Bypass Override Bit will be true when the Manual Bypass Override input is true.

 

 

Table 6.5 Parameter 31-10 Bypass Status Word Bit Definitions

BAS-SVX49A-EN

6-9

Page 61
Image 61
Trane Vertical Bypass/Non Bypass Panel, TR200 Mode of Operation Select, Par. No, Selection, Function, Description