3.1.3 Internal Main Panel Fuses

Installation

3.1.3 Internal Main Panel Fuses

Use only the specified fuse or an equivalent replacement for the internal main fuses. See the specifications label inside the cover of the unit for acceptable replacement main fuses. A sample of this can be seen in Table 3.6.

Fuse

 

Description

Manufacturer

Part Number/Size

F13A & C

 

Primary Transformer

Bussmann

FNQ-R-0.50

F15A, B, & C

 

Main Fuses

Bussmann

LPJ-30-SP

 

 

 

 

 

F16A, B, & C

 

Drive Fuses

Bussmann

JJS-35

 

 

 

 

 

F900, F901,F902

 

SMPS - Power Supply

Bussmann

FWH-020A6F, 500V

 

 

 

 

 

Table 3.6 Sample Fuse Rating Label

 

 

 

3.2Mechanical Installation 3.2.1 Lifting

3.2Mechanical Installation 3.2.1 LiftingHeavy Objects!WARNING

Heavy Objects!

Do not use cables (chains or slings) except as shown. Each of the cables (chains or slings) used to lift the unit must be capable of supporting the entire weight of the unit. Lifting cables (chains or slings) may not be of the same length.

Adjust as necessary for even unit lift. Other lifting arrangements may cause equipment or property-only damage. Failure to properly lift unit could result in death or serious injury. See details below.

3.2.3 Forklift

Only a competent lift operator with additional support personnel should attempt moving the unit.

Carefully position forklift and ensure stability prior to lift.

3.2.4 Shipping Weights

Weights listed in Table 3.7 are approximate for base units. Options can add or reduce weight of unit. Weights listed are in lbs.

3.2.3 Forklift3.2.4 Shipping WeightsWARNING

Check the weight of unit to determine the safety of the lifting method. Ensure that the lifting device is suitable for the task. If necessary, plan for a hoist, crane or forklift with appropriate rating to move the units.

Follow recommendations below. failure to do so could result in death or serious injury.

Frame

Non Bypass Panel

Bypass Panel

 

 

 

P2

36

84

 

 

 

P3

66

106

 

 

 

P4

106

167

 

 

 

P5

155

248

Table 3.7 Approximate Shipping Weights

3.2.2 Hoist or Overhead Lift

Use a solid steel spreader bar for lifting. Slide the spreader bar through the two (2) lifting holes on the panel. Lifting rings are 0.59in (15mm) in diameter (see Figure 3.1). If VFD mounting screws interfere with the spreader bar, lifting hooks can be used instead of the lifting bar.

Connect the spreader bar to a hoist or other lifting device.

Carefully lift the unit and secure it to the wall. Refer to 8 Appendix for dimensional drawings to determine fasteners size and location.

BAS-SVX49A-EN

3-3