Figure 3.2 Side Cooling Clearance

Installation

Figure 3.2 Side Cooling Clearance

Figure 3.1 Proper Lifting Method

3.3 Cooling

Only mount the drive and panel vertically.

Panels rely on the ambient air for cooling. It is important to observe the limitations on ambient air temperature. The maximum ambient temperature for all bypass panels is 40°C and

45°C for non bypass panels. Derating concerns start above 3300 feet elevation above sea level.

Most panels may be mounted side-by-side without additional side clearance. However, the P2 (B3 frame size) units require 1.5 in. minimum clearance between units (see Figure 3.2).

Top and bottom clearance is required for cooling (see Figure 3.3). Generally, 2 to 10 inches (50 to 250mm) minimum clearance is required, depending upon the hp (kW) of the unit. See the dimensional drawings in 8 Appendix for specific requirements.

No additional back plate is required for drives with the bypass and non bypass panels.

Figure 3.3 Cooling Airflow