Trane Vertical Bypass/Non Bypass Panel Wire and Cable Access, Hazardous Voltage, Installation

Models: TR200 Vertical Bypass/Non Bypass Panel

1 86
Download 86 pages 30.73 Kb
Page 29
Image 29
3.4.2 Wire and Cable Access

Installation

3.4.2 Wire and Cable Access

•IMPORTANT NOTEWARNING

Hazardous Voltage!

Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power cannot be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury.

Refer to through for wire routing and termination locations.

Removable access knockout covers are provided for cable connections (see Figure 3.13 and Figure 3.14).

Access holes are provided for input power, motor leads, and control wiring.

Figure 3.13 Bypass Panel Conduit Entry Diagram

Run input power, motor wiring, and control wiring in three separate conduits for isolation.

NOTE!

IMPORTANT NOTE

RUN INPUT POWER, MOTOR WIRING AND CONTROL WIRING IN THREE SEPARATE METALLIC CONDUITS OR RACEWAYS FOR HIGH FREQUENCY NOISE ISOLATION. FAILURE TO ISOLATE POWER, MOTOR AND CONTROL WIRING COULD RESULT IN LESS THAN OPTIMUM DRIVE AND ASSOCIATED EQUIPMENT PERFORMANCE.

The drive always resides in the upper section of the panel. Connections to the ECB and EMB2 are in this area except on the P2 bypass panels.

Power connections are typically towards the bottom side of the panel.

Control wiring should be isolated from power components inside the unit as much as possible. Trane has included hardware to allow for the separation.

Figure 3.14 Non Bypass Panel Conduit Entry Diagram

See the mechanical layout drawings in through for connection details and recommended wire routing.

BAS-SVX49A-EN

3-15

Page 29
Image 29