Trane TR200 specifications Start Up Troubleshooting, Symptom, Possible cause, Test, Solution

Models: TR200 Vertical Bypass/Non Bypass Panel

1 86
Download 86 pages 30.73 Kb
Page 70
Image 70
Manual background

Start Up Troubleshooting

Symptom

Possible cause

Test

Solution

 

 

 

 

 

Motor overloaded

Motor is drawing too much current for

Perform startup and verify motor current

 

 

the application.

is within specifications. If not, reduce the

 

 

 

load on the motor.

 

Loose connections

Look for signs of overheating on

Perform pre-startup check for loose

Overload trips

 

connections to OL.

connections and tighten. Replace any

 

 

 

overheated components and wires.

 

OL not set correctly

An improperly set OL can cause the OL

Set correct motor current on OL.

 

 

to trip too soon. See pre-startup

 

 

 

procedure for correct setting.

 

 

Contamination

Remove contactor and check for

If contamination is found, repair or

 

 

contamination.

replace.

Contactor fails

Defective coil

Compare coil resistance to contactor

If readings are not the same or if there

 

specification. Inspect the coil for signs

are visible signs of damage, replace the

to pull in

 

 

of overheating and damages.

coil or contactor.

 

 

 

Auxiliary contact binding action

Remove auxiliary contacts and test

If contactor operates with auxiliaries

 

 

contactor action.

removed, replace auxiliary contacts.

 

 

 

 

 

Contamination

Remove the contactor and check for

If contamination is found, repair or

 

 

contamination.

replace.

 

 

 

 

Contactor fails

Defective coil

Compare coil resistance to functional

If readings are not the same or there are

 

contactors of the same size.

visible signs of damage, replace the coil

to drop out

 

 

 

or contactor.

 

 

 

 

 

 

 

 

Auxiliary contact binding action

Remove auxiliary contacts and test

If the contactor operates with auxiliaries

 

 

contactor action.

removed, replace auxiliary contacts.

 

 

 

 

 

Problem with mains power

Rotate incoming power leads into

If the imbalanced leg follows the wire, it

 

 

option panel one position; A to B, B to

is a power problem. Causes can vary.

Mains current

 

C, and C to A.

Contact an electrician or power expert

imbalance

 

 

for a solution.

greater than

Problem with option panel

Rotate incoming power leads into

If the imbalanced leg stays on the same

3%

 

option panel one position; A to B, B to

option panel input terminal, it is a

 

 

C, and C to A.

problem with the option panel. Contact

 

 

 

the factory for assistance.

 

 

 

 

 

Problem with motor or motor wiring

Rotate outgoing motor leads one

If the imbalanced leg follows the motor

 

 

position; U to V, V to W, and W to U.

lead, the problem is in the motor or

Motor current

 

 

wiring to the motor. Causes can vary.

 

 

Contact an electrician or motor expert

imbalance

 

 

 

 

for a solution.

greater than

 

 

 

 

 

Problem with option panel

Rotate outgoing motor leads one

If the imbalanced leg stays on the same

3%

 

position; U to V, V to W, and W to U.

option panel output terminal, it is a

 

 

 

 

 

problem with the option panel. Contact

 

 

 

the factory for assistance.

 

 

 

 

7-4

BAS-SVX49A-EN

Page 70
Image 70
Trane TR200, Vertical Bypass/Non Bypass Panel Start Up Troubleshooting, Symptom, Possible cause, Test, Solution