Table 3.13 Tightening Torques, 460V

BAS-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

460 VAC

 

 

 

 

 

 

 

 

SVX49A-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Input

Output

 

Input

 

 

Output

 

 

 

 

 

 

 

Non Bypass

 

 

 

Bypass

 

 

 

 

 

EN

 

 

Panel (TR200) Non Bypass

 

 

 

 

 

 

 

 

 

 

 

Ground Wire

HP (KW)

Drive Disconnect

 

 

Disconnect Switch

Disconnect Switch

Circuit Breaker L1,

Single Motor

 

 

 

 

& Bypass

Motor T1, T2, & T3

(w/o Fuses) UL508A

Fusible UL98 L1, L2,

Overload T1, T2, &

Torque lb-in (N-m)

 

 

 

Switch L1, L2, & L3

L2, & L3 Torque lb-

 

 

 

 

Torque lb-in (N-m)

L1, L2, & L3 Torque

& L3 Torque lb-in (N-

T3 Torque lb-in (N-

 

 

 

 

 

 

Torque lb-in (N-m)

in (N-m)

 

 

 

 

 

 

 

 

lb-in (N-m)

 

m)

 

m)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

15

(11)

 

55

(6.2)

16

(1.8)

7 (0.8)

30

(3.3)

40

(4.5)

24

(2.7)

40

(4.5)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

20

(15)

P2

55

(6.2)

16

(1.8)

7 (0.8)

30

(3.3)

40

(4.5)

24

(2.7)

40

(4.5)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

25 (18.5)

 

55

(6.2)

16

(1.8)

7 (0.8)

30

(3.3)

45 (5)

24

(2.7)

40

(4.5)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

30

(22)

 

55

(6.2)

40

(4.5)

18 (2)

30

(3.3)

45 (5)

50

(5.6)

40

(4.5)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40

(30)

P3

55

(6.2)

40

(4.5)

18 (2)

120

(13.5)

50

(5.6)

50

(5.6)

40

(4.5)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

50

(37)

 

55

(6.2)

40

(4.5)

18 (2)

120

(13.5)

50

(5.6)

50

(5.6)

40

(4.5)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

60

(45)

P4

70

(7.9)

88.5 (10)

55 (6.2)

200

(22.5)

50

(5.6)

50

(5.6)

40

(4.5)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

75

(55)

200

(22.5)

88.5 (10)

200 (22.5)

200

(22.5)

50

(5.6)

50

(5.6)

40

(4.5)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

100 (75)

P5

200

(22.5)

124 (14)

200 (22.5)

200

(22.5)

274 (31)

275 (31)

40

(4.5)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

125 (90)

200

(22.5)

124 (14)

200 (22.5)

500

(56.5)

274 (31)

275 (31)

40

(4.5)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 3.13 Tightening Torques, 460V

3-23

Installation

Page 37
Image 37
Trane Vertical Bypass/Non Bypass Panel, TR200 Installation, 460 VAC, Output, Ground Wire, Hp Kw, 13 Tightening Torques