Parameter

Parameter name

Setting title

Setting

Function

 

 

 

 

 

5-01

Term 27 Mode

Input

0

Customer Interlock

5-02

Term 29 Mode

Output

1

Auto bypass

5-10

Term 18 digital input

Start

8

Common run/stop

5-11

Term 19 digital input

Run Permissive

52

Run Permissive

5-12

Term 27 digital input

External Interlock

7

Customer Interlock

 

 

 

 

 

5-31

Term 29 digital output

No Alarm

160

Auto bypass

 

 

 

 

 

5-40(0)

Relay 1 function

Start Command Active

167

Run Permissive

 

 

 

 

 

5-40(0)

Relay 1 off delay

Off Delay

0.00 S

Run Permissive

 

 

 

 

 

Table 6.1 Parameter Group 5-** Factory Default Settings

6.1.2 ECB Control Card

The ECB control card (see Figure 6.2) provides input connector X57 for commanding bypass operation remotely and output connector X59 for reporting the bypass mode of operation, either drive mode or running in bypass.

See Table 6.2 for ECB control card terminal types and functions.

1

2

3

4

1.Terminal X58

2.Terminal X56

3.Terminal X57

4.Terminal X59

130BX232.10

6-2

BAS-SVX49A-EN

Page 54
Image 54