1.6.4 Panel Voltage and Frame Ratings

Introduction

1.6.4 Panel Voltage and Frame Ratings

Table 1.4Table 1.4 defines the voltage and hp ratings of the frames sizes for the panel. See 8 Appendix for overall and mounting dimensions.

Panel P2

Bypass

 

Non Bypass

(B3 - Drive)

TR200

 

TR200

Volts VAC

 

HP (KW)

 

 

 

 

208

& 230

7.5 (5.5) - 15 (11)

7.5 (5.5) - 15 (11)

 

 

 

 

460

& 600

15 (11) - 25 (18.5)

15 (11) - 25 (18.5)

Panel P3

Bypass

 

Non Bypass

(B4 - Drive)

TR200

 

TR200

 

 

 

 

Volts VAC

 

HP (KW)

 

 

 

 

208

20 (15)

 

20 (15) - 25 (18.5)

 

 

 

230

20 (15) - 25 (18.5)

 

 

 

 

 

 

460 & 600

30 (22) - 50 (37)

30 (22) - 50 (37)

Panel P4

Bypass

 

Non Bypass

(C3 - Drive)

TR200

 

TR200

 

 

 

 

 

 

Volts VAC

 

 

HP (KW)

 

208

25 (18.5)

 

30 (22)

- 40 (30)

230

30 (22)

- 40 (30)

 

 

 

 

460 & 600

60 (45)

- 75 (55)

60 (45)

- 75 (55)

Panel P5

 

Bypass

 

Non Bypass

(C4 - Drive)

 

TR200

 

 

TR200

 

 

 

 

 

 

 

 

Volts VAC

 

 

 

HP (KW)

 

 

 

 

 

 

 

 

 

 

 

208

& 230

50

(37)

- 60 (45)

 

50

(37)

- 60 (45)

 

 

 

 

 

 

 

 

 

460

& 600

100

(75)

- 125 (90)

 

100

(75)

- 125 (90)

 

 

 

 

 

 

 

 

 

Table 1.4 Panel Voltage and Frame Ratings

1.7Power Component Functions 1.7.1 Power Fusing

For main panel power fuses, only use the specified fuse or an equivalent replacement. For drive fuses only use the specified fuse. See the fuse ratings label on the inside cover of the unit or Table 3.2Table 3.2, Table 3.3Table 3.3, Table 3.4Table 3.4 and Table 3.5Table 3.5.

Main fusing

Main fuses are located ahead of the drive and bypass. Main fuses are designed to protect the circuitry within the bypass panel but is not adequate to protect the drive. Main fuses are dual-element, time-delay types and mount inside the bypass enclosure.

Drive fusing

Drive fuses are located ahead of the drive and are a fast- acting type. Drive fuses are standard in all bypass and non- bypass panels.

5,000 or 100,000 amp SCCR

The bypass panel supplied with a non fusible Main Disconnect Switch is 5,000 amps short-circuit current rating (SCCR). The bypass panel supplied with a Fusible disconnect or circuit breaker is 100,000 amp SCCR. The non bypass panel supplied with a non-fusible Main Disconnect is 100,000 amp SCCR. See the panel label for SCCR rating.

NOTE!

The 600 V circuit breaker option is 5,000 amp (SCCR).

1-6

BAS-SVX49A-EN