3.4.4 Wire Type Rating

Installation

460 VAC

 

 

 

Panel (TR200) Non Bypass

Maximum Field

Field Ground

Minimum Temperature

HP (KW)

UL Motor Current

Wiring Size Class B

Wiring Size Class B

Wire Rating "°C" Copper

& Bypass

 

 

 

or C

or C

Conductor

 

 

 

 

 

 

 

 

 

 

 

15

(11)

21

 

10 AWG

10 AWG

60

 

 

 

 

 

 

 

20

(15)

27

P2

8 AWG

10 AWG

60

 

 

 

 

 

 

25 (18.5)

34

 

6 AWG

10 AWG

60

 

 

 

 

 

 

 

30

(22)

40

 

6 AWG

10 AWG

60

 

 

 

 

 

 

 

40

(30)

52

P3

4 AWG

10 AWG

60

 

 

 

 

 

 

 

50

(37)

65

 

3 AWG

8 AWG

60

 

 

 

 

 

 

 

60

(45)

77

P4

1 AWG

8 AWG

60

 

 

 

 

 

 

75

(55)

96

1 AWG

8 AWG

60

 

100

(75K)

124

P5

2/0 AWG

6 AWG

75

125 (90)

156

3/0 AWG

6 AWG

75

 

 

 

 

600 VAC

 

 

 

 

 

Panel (TR200) Non Bypass

Maximum Field

Field Ground

Minimum Temperature

HP (KW)

UL Motor Current

Wiring Size Class B

Wiring Size Class B

Wire Rating "Degree C"

& Bypass

 

 

 

or C

or C

Copper Conductor

 

 

 

 

15

(11)

17

 

10 AWG

10 AWG

60

 

 

 

 

 

 

 

20

(15)

22

P2

10 AWG

10 AWG

60

 

 

 

 

 

 

25 (18.5)

27

 

8 AWG

10 AWG

60

 

 

 

 

 

 

 

30

(22)

32

 

8 AWG

10 AWG

60

 

 

 

 

 

 

 

40

(30)

41

P3

6 AWG

10 AWG

60

 

 

 

 

 

 

 

50

(37)

52

 

4 AWG

10 AWG

60

 

 

 

 

 

 

 

60

(45)

62

P4

3 AWG

8 AWG

60

 

 

 

 

 

 

75

(55)

77

1 AWG

8 AWG

60

 

 

 

 

 

 

 

100 (75)

99

P5

1 AWG

8 AWG

60

 

 

 

 

 

 

125 (90)

125

2/0 AWG

6 AWG

75

 

 

 

 

 

 

 

 

Table 3.10 Wire Size Chart 460 and 600 V

3.4.4 Wire Type Rating

The wire style rating specifications are provided inTable 3.9 and Table 3.10

3.4.5 Terminal Tightening Torques

Tighten all connections to the torque specifications provided in Table 3.11 and Table 3.13

The torque specifications are also located on the tightening torque and wire rating label inside the panel cover. See Table 3.15 for a sample of the torque and wire rating data.