– 7 – |
Installation Manual |
Weight centre and weight
◆Weight centre of an outdoor unit
(A) |
|
| (B) |
|
|
| Anchor bolt position |
Anchor bolt position |
|
| 920 |
700 |
|
|
|
bolt position 755 |
| bolt position | 755 |
Anchor | Y | Anchor | Y |
XX
Z | Z |
No. | Model type | X (mm) | Y (mm) | Z (mm) | Weight (kg) | ||
Heat pump model | Cooling only model | ||||||
|
|
|
|
| |||
| MAP080 |
|
|
|
|
| |
|
|
|
|
|
|
| |
(A) | MAP100 | 500 | 390 | 645 | 242 | 241 | |
|
|
|
|
|
|
| |
| MAP120 |
|
|
|
|
| |
|
|
|
|
|
|
| |
(B) | MAP140 | 605 | 350 | 700 | 330 | 330 | |
| |||||||
MAP160 | |||||||
|
|
|
|
|
|
Installation Manual |
6 INSTALLATION OF THE OUTDOOR UNIT
WARNING
•Be sure to install the outdoor unit in a place able to bear its weight. If strength is insufficient, the unit may fall down resulting in human injury.
•Perform specified installation work to protect against strong wind and earthquakes. If the outdoor unit is imperfectly installed, an accident by falling or dropping may be caused.
CAUTION
•Drain water is discharged from the outdoor unit. (Especially while heating) Install the outdoor unit in a place with good drainage.
•For installation, be careful of the strength and level of the foundation so that abnormal sounds (vibration or noise) are not generated.
REQUIREMENT
Installation in a snowfall area
1.Install the outdoor unit on a higher foundation than the snowfall or set up a stand to install the unit so that snowfall will not affect the unit.
•Set up a stand higher than the snowfall.
•Apply an angled structure to the stand so that drainage will not be prevented. (Avoid using a stand with a flat surface.)
2.Mount a
•Leave enough space for the
(4 faces)
(locally procured)
Stand
(locally procured)
1.To install multiple outdoor units, arrange them with 20mm or more spaces in between.
Fix each outdoor unit with M12 anchor bolts at 4 positions. 20mm projection is appropriate for an anchor bolt.
20mm or more | 20mm or more |
20
M12 anchor bolt
4 positions/unit