Installation

TCP Base to Interior Wall Section Assembly (Typical)

Note: Failure to completely compress the gasketing may result in air leakage.

1Join the two units and secure with field provided 5/8-inch flat washers and 5/8-inch X 2-1/2-inch grade 9 bolts though each of the six holes.

2Apply caulk the length of the base between the 2-inch X 2-inch angle on the one base section and the wall on the adjoining section. See Illustration below. Note: Use a polyurethane or equivalent caulk.

3Secure the 2-inch X 2-inch angle to the adjoining wall with number 14 sheet-metal crews on 12-inch centers along the length of the angle and wall.

Figure 8. TCP base to interior wall sections

INTERIOR WALL

SPLIT

4" X 1/4" GASKET

SECURE 2" X 2" ANGLE TO WALL W/#14 S.M. SCREWS @ 12" CTR'S

CAULK

SPLIT

INTERIOR

 

WALL

CAULK

 

 

CAULK

SPLIT

SPLIT

BASE TO WALL ASSEMBLY COMPLETE