Trane CAH-SVX01A-EN TCP Model Assembly Instructions, Joining Sections Edge-to-Edge, Installation

Models: CAH-SVX01A-EN Custom Climate Changer Air Handlers

1 60
Download 60 pages 9 Kb
Page 12
Image 12
TCP Model

Installation

TCP Model

Assembly

Instructions

If your nameplate model number begins with TCP, use the assembly instructions below.

Joining Sections Edge-to- Edge

Units must be installed level for proper drainage of condensate from the drain pan. In addition, each section in a multi-section unit must be properly supported.

Note: Leveling each section, beginning with the first, is critical. Failure to level and align the sections immediately creates greater

two sections should be within 12 inches to reduce the amount of dragging required.

6Remove lifting lugs on mating section as required.

7Insert threaded rods through each hole of each mating connecting plate (see Figure 4). Bring each connecting surface together uniformly until gasketing is contacted.

Note: Use field provided threaded rods inserted in all holes of each connecting plate to prevent damage and distortion of the sections as they are joined. Tighten all rods in sequence. Do not try to join sections by tightening only some of the rods.

Note: Failure to compress the gasketing may result in air leakage.

8Secure the unit sections at the base using the field provided bolts, nuts and washers at the connecting plates.

9Once the sections are pulled together, install the assembly hardware as applicable for the walls, roof, and the base as demonstrated in the following assembly sections.

misalignment or even structural damage afterward.

1Remove all crating and wrapping from the surfaces to be joined.

2Place one section of the air handler into the desired position. Verify each section is level and properly supported prior to proceeding with assembly. Each unit must be level side-to-side and front to back. Check squareness measuring the critical dimensions given.

3When the unit is positioned and squareness is assured within 1/8- inch, remove all lifting lugs located along the split plane.

4Install 4-inch x 1/4-inch neoprene gasket to all mating surfaces of the section, including the internal walls. This gasket must be applied to the full perimeter of the section split of both sections to be joined.

5Move the next mating section into alignment with the positioned section. Alignment of sections must be completed before gasket surfaces meet. The

Figure 4. Insert threaded rods through each hole of mating connecting plate.

12

CAH-SVX01A-EN

Page 12
Image 12
Trane CAH-SVX01A-EN manual TCP Model Assembly Instructions, Joining Sections Edge-to-Edge, Installation