Trane CAH-SVX01A-EN manual Air Filters, Installation, WARNING Hazardous Voltage with Capacitors

Models: CAH-SVX01A-EN Custom Climate Changer Air Handlers

1 60
Download 60 pages 9 Kb
Page 26
Image 26
Air Filters

Installation

Air Filters

Front Load Filters

Most filters in custom units are installed in unitary sheet metal frames. Filters are secured with a metal clip. There are several different styles.

To install filters:

1Disconnect power to the unit.

2Open or remove the filter clip.

3Remove the filter from the rack.

4Install new filters with the directional arrows pointing in the direction of airflow.

5Secure the filter using the appropriate clip for each filter.

Review Figure 21 through Figure 24 for an explanation of the methods for securing the different types of filters.

The filters are often installed in a pre/post filter configuration. Be sure to note the order of installation.

Note: Filters must have an airtight seal to prevent air bypass.

￿WARNING Hazardous Voltage with Capacitors!

Disconnect all electric power, including remote disconnects and discharge all motor start/run capacitors before servicing. Follow proper lockout/tagout procedures to ensure the power cannot be inadvertently energized. For variable frequency drives or other energy storing components provided by Trane or others, refer to the appropriate manufacturer’s literature for allowable waiting periods for discharge of capacitors. Verify with an appropriate voltmeter that all capacitors have discharged. Failure to disconnect power and discharge capacitors before servicing could result in death or serious injury.

Figure 21. C-70 fastener holds 2-inch filter

Figure 22. C-86 fastener (shown) or C- 77 fastener holds 4-inch pleated filters

Figure 23. Bag filter show with C-70 fastener

Figure 24. C-80 spring fastener secures cartridge

Side Load Filters

Most filters in custom units are installed in unitary sheet metal frames. If unit is provided with side access rack, do the following for installation:

2-inch or 4-inch flat filters.

1Disconnect the power to the unit.

2Open the filter section access door and remove the filters and block-offs from their installed position.

3Slide the filter into the rack.

4Some side load racks will be provided with block-off plates. Install them into the rack last before closing the door.

5Close and secure the door, making certain the door closes snug against the block-off (see Figure 25).

26

CAH-SVX01A-EN

Page 26
Image 26
Trane CAH-SVX01A-EN manual Air Filters, Installation, WARNING Hazardous Voltage with Capacitors