3Check that the bushing on the isolator stud is centered in the isolator. Adjust to center by moving the stud in the fan base hole.

4This procedure will raise the equipment load until the isolators are all off the shims (shipping tie-down blocks) approximately 1/32-inch (the thickness of a credit card), and the internal gap is approximately equal to the external gap.

Note: Do not adjust isolators once the fan base is off of the shipping tie down blocks.

5Continue adjusting other isolators in sequence and repeat the same adjustment. Continue until all isolators are adjusted.

6Replace the jam nut on each isolator adjusting bolt, tighten the nut, and remove the shipping tie down block.

Traq™ Dampers

Traq dampers are low-leak dampers that modulate and measure airflow. Each Traq damper module is supplied with a factory-mounted ventilation control module (VCM) on the interior of the mixing box module. The VCM has an input terminal for power and an output terminal for air velocity (see Figure 20).

Installation

The actuators, factory-mounted or field-supplied, are separately wired and controlled by a direct-digital controller or other building logic.

VCM (Transducer) Calibration. The VCM has an auto-zero function that recalibrates the transducer once every minute.

Input Power Signal. The only input signal the VCM needs is the 24 Vac power connected to terminals 1TB1- 5 and 1TB1-6.

Output Velocity Signal. The

2 to 10 VDC linear output signal from the VCM represents air velocity. This voltage can be converted to represent airflow (cfm or L/s) using the formula below, Table 1 and data in your submittal package.

Airflow = k (cfm @ 10V)

(------------------------------volts2)

 

8

OR

 

Airflow = k (L/s @ 10V)

(------------------------------volts2)

 

8

Altitude can be adjusted for by using the following factors:

Table 1. Altitude adjustment factors

Sea level = 1.0

Elevation (feet)

k

 

 

1000

0.982

2000

0.964

3000

0.949

4000

0.930

5000

0.914

6000

0.897

7000

0.876

8000

0.860

9000

0.846

10,000

0.825

 

 

Control Dampers

If the damper actuators are not factory mounted install damper actuators and connecting linkage. Check damper operation and linkage alignment.

Damper blades should be non- binding. Adjust damper frame as necessary to ensure free blade movement.

Magnahelic Air Filter Gage

Check zero adjustment of the gage. Turn both vent valves to the “Vent” position and adjust the gage pointer to zero by means of the external adjustment screw in the face of the gage. After zeroing, turn the vent valves to the “Line” position.

Figure 20. Traq damper terminal connections

Ventilation Control

Module

Velocity (2–10 Vdc) 1TB1–3

GND

 

1TB1–4

 

24 Vac 1TB1–5

GND 1TB1–6