Trane BACnet Option Module How to Configure the System, Control Word Timeout Function, Bibbs

Models: TR200

1 56
Download 56 pages 40.28 Kb
Page 23
Image 23
How to Configure the System

How to Configure the System

Digital/Bus settings

 

Name

Par. Number

Default Value

Setting for BACnet

 

 

 

Coasting Select

8-50

Logic-or

Logic-or

 

 

 

Quick Stop Select

8-51

Logic-or

Logic-or

 

 

 

DC Brake Select

8-52

Logic-or

Logic-or

 

 

 

Start Select

8-53

Logic-or

Logic-or

 

 

 

Reversing Select

8-54

Logic-or

Logic-or

 

 

 

Set-up Select

8-55

Logic-or

Logic-or

 

 

 

Preset reference Select

8-56

Logic-or

Logic-or

 

 

 

 

 

 

 

 

 

BACnet settings

 

 

 

 

 

 

Name

Par. Number

Default Value

Setting for BACnet

 

 

 

BACnet device instance

8-71

1

1

 

 

 

MS/TP Max Masters

8-73

127

Depent on the Number of

 

 

 

Masters in the system

 

 

 

 

 

 

 

 

 

“I am” Service

8-74

At power-up

At power-up

 

 

 

Initialization Password

8-75

“admin”

“admin”

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Control Word Timeout Function

par.8-03Control Timeout Time and par.8-04Control Timeout Function are not enabled in this version of the BACnet option.

BIBBs

Bibb's

ReadProperty Service

ReadPropertyMultiple Service

WriteProperty Service

WritePropertyMultiple Service

ConfirmedEventNotification Service

UnconfirmedEventNotification Service

GetEventInformation Service

AcknowledgeAlarm Service

ReinitializeDevice Service

DeviceCommunicationControl Service

I-Have Service

Who-Has Service

Who-Is Service

I-am Service

TimeSynchronization

4-2

TR200 BACnet

Page 23
Image 23
Trane BACnet Option Module, TR200 instruction manual How to Configure the System, Control Word Timeout Function, Bibbs