How to Control the Adjustable Frequency Drive

Object

 

Read /

Change-

Non-vola-

 

Alarm

Object Name

able De-

tile RAM

Drive Par.

notifi-

ID

Write

 

scription

Store

 

cation

 

 

 

 

BV:80

Broken Belt

R

No

NA

16-91/08

Yes

BV:81

Discharge High

R

No

NA

16-91/08

Yes

BV:82

Start Fault

R

No

NA

16-91/10

Yes

BV:83

Speed Limit

R

No

NA

16-91/11

Yes

BV:84

State Fault P

R

No

NA

16-91/12

Yes

1691/12

 

 

 

 

 

 

BV:85

State Fault P

R

No

NA

16-91/13

Yes

1691/13

 

 

 

 

 

 

BV:86

State Fault P

R

No

NA

16-91/14

Yes

1691/14

 

 

 

 

 

 

BV:87

State Fault P

R

No

NA

16-91/15

Yes

1691/15

 

 

 

 

 

 

BV:88

KTY Temperature

R

No

NA

16-91/16

Yes

Error

 

 

 

 

 

 

BV:89

Drive Fan Error

R

No

NA

16-91/17

Yes

BV:90

ECB Error

R

No

NA

16-91/18

Yes

BV:91

Alarm 1692/19

R

No

NA

16-91/19

Yes

BV:92

Alarm 1692/20

R

No

NA

16-91/20

Yes

BV:93

Alarm 1692/21

R

No

NA

16-91/21

Yes

BV:94

Alarm 1692/22

R

No

NA

16-91/22

Yes

BV:95

Alarm 1692/23

R

No

NA

16-91/23

Yes

BV:96

Alarm 1692/24

R

No

NA

16-91/24

Yes

BV:97

Alarm 1692/25

R

No

NA

16-91/25

Yes

BV:98

Alarm 1692/26

R

No

NA

16-91/26

Yes

BV:99

Alarm 1692/27

R

No

NA

16-91/27

Yes

BV:100

Alarm 1692/28

R

No

NA

16-91/28

Yes

BV:101

Alarm 1692/29

R

No

NA

16-91/29

Yes

BV:102

Alarm 1692/30

R

No

NA

16-91/30

Yes

BV:103

Alarm 1692/31

R

No

NA

16-91/31

Yes

BV:104

Brake Check

R

No

NA

16-92/00

Yes

BV:105

Pwr. Card Temp

R

No

NA

16-92/01

Yes

BV:106

Ground Fault

R

No

NA

16-92/02

Yes

BV:107

Ctrl. Card Temp

R

No

NA

16-92/03

Yes

BV:108

Crtl. Word TO

R

No

NA

16-92/04

Yes

BV:109

Overcurrent

R

No

NA

16-92/05

Yes

BV:110

Torque Limit

R

No

NA

16-92/06

Yes

BV:111

Motor Th Over

R

No

NA

16-92/07

Yes

BV:112

Motor ETR Over

R

No

NA

16-92/08

Yes

BV:113

Inverter Overld.

R

No

NA

16-92/09

Yes

BV:114

DC undervolt

R

No

NA

16-92/10

Yes

BV:115

DC overvolt

R

No

NA

16-92/11

Yes

BV:116

DC Voltage Low

R

No

NA

16-92/12

Yes

BV:117

DC Voltage high

R

No

NA

16-92/13

Yes

BV:118

Line ph. loss

R

No

NA

16-92/14

Yes

BV:119

No Motor

R

No

NA

16-92/15

Yes

BV:120

Live Zero Error

R

No

NA

16-92/16

Yes

Triggers Bus

Timeout

Table 5. 10: Binary values cont.