How to Control the Adjustable Frequency

Drive

 

 

Object

Object Name

Read/

Change-

Non-vola-

TR200Pa-

Alarm

Triggers Bus

 

 

 

 

ID

Write

able De-

tile RAM

rameter

notifi-

Timeout

 

 

 

 

 

scription

Store

cation

 

 

 

 

 

 

 

 

 

 

 

 

 

AV:0

Reference

W/R

Yes

No

MRV

No

Yes

 

 

 

 

AV:1

Speed Act. Value

W/R

Yes

No

MAV

Yes

Yes

 

 

 

 

AV:2

Bus Feedback1

W/R

Yes

No

8-94

No

Yes

 

 

 

 

AV:3

Bus Feedback2

W/R

Yes

No

8-95

No

Yes

 

 

 

 

AV:4

Bus Feedback3

W/R

Yes

No

8-96

No

Yes

 

 

 

 

AV:5

Motor Voltage

Read

Yes

No

16-12

Yes

No

 

 

 

 

AV:6

Motor Current

Read

Yes

No

16-14

Yes

No

 

 

 

 

AV:7

Motor Torque %

Read

Yes

No

16-22

Yes

No

 

 

 

 

AV:8

DC Link Voltage

Read

Yes

No

16-30

Yes

No

 

 

 

 

AV:9

Motor Thermal

Read

Yes

No

16-18

Yes

No

 

 

 

 

AV:10

Heatsink Temper-

Read

Yes

No

16-34

Yes

No

 

 

 

 

ature

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AV:11

Inverter Thermal

Read

Yes

No

16-35

Yes

No

 

 

 

 

AV:12

Operating Hours

Read

No

No

15-00

No

No

 

 

 

 

AV:13

Running Hours

Read

No

No

15-01

No

No

 

 

 

 

AV:14

KWh Counter

Read

No

No

15-02

No

No

 

 

 

 

AV:15

Power [KW]

Read

No

No

16-10

No

No

 

 

 

 

AV:16

PID Start Speed

W/R

No

TR200

20-83

No

No

 

 

 

 

[Hz]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AV:17

PID Proportional

W/R

No

TR200

20-93

No

No

 

 

 

 

Gain

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AV:18

PID Integral Time

W/R

No

TR200

20-94

No

No

 

 

 

 

(Sec)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AV:19

PID Differential

W/R

No

TR200

20-95

No

No

 

 

 

 

Time (Sec)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AV:20

PID Dif. Gain Limit

W/R

No

TR200

20-96

No

No

 

 

 

 

AV:21

On Reference

W/R

No

TR200

20-84

No

No

 

 

 

 

Bandwith

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AV:22

Ext. 1 Setpoint

W/R

No

TR200

21-15

No

No

 

 

 

 

AV:23

Ext. 1 Reference

W/R

No

TR200

21-17

No

No

 

 

 

 

[Unit]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AV:24

Ext. 1 Feedback

W/R

No

TR200

21-18

No

No

 

 

 

 

[Unit]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AV:25

Ext. 1 Proportion-

W/R

No

TR200

21-21

No

No

 

 

 

 

al Gain

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AV:26

Reserved

W/R

No

Na

 

 

 

 

 

 

 

AV:27

Ext. 1 Integral

W/R

No

TR200

21-22

No

No

 

 

 

 

Time (Sec)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AV:28

Ext. 1 Differential

W/R

No

TR200

21-23

No

No

 

 

 

 

Time (Sec)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AV:29

Ext. 1 Dif. Gain

W/R

No

TR200

21-24

No

No

 

 

 

 

Limit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AV:30

Reserved

W/R

No

Na

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 5. 3: Analog values

TR200 BACnet

5-3

Page 28
Image 28
Trane TR200, BACnet Option Module instruction manual Rameter Notifi Timeout Scription