How to Control the Adjustable Frequency

Drive

Network Adjustable Frequency Drive Control Inputs and Outputs

Analog Input and Output Objects

Control the adjustable frequency drive from the BACnet network using 'objects'. The various types of 'objects' and their descriptions are shown in the following tables.

Object

Object Name

Read/

ID

Write

 

AI:0

Analog

R

Input 53

 

 

AI:1

Analog

R

Input 54

 

 

AI:2

Analog

R

In X30/11

 

 

AI:3

Analog

R

In X30/12

 

 

AI:4

Analog

R

Input X42/1

 

 

AI:5

Analog

R

Input X42/3

 

 

AI:6

Analog

R

Input X42/5

 

 

Change-

Non-vola-

 

Alarm

Triggers bus

able De-

tile RAM

Drive Par.

notifi-

timeout

scription

Store

 

cation

 

 

Yes

No

16-62

Yes

NO

 

 

 

 

 

Yes

No

16-64

Yes

NO

 

 

 

 

 

Yes

No

16-75

Yes

NO

 

 

 

 

 

Yes

No

16-76

Yes

NO

 

 

 

 

 

Yes

No

18-30

Yes

NO

 

 

 

 

 

Yes

No

18-31

Yes

NO

 

 

 

 

 

Yes

No

18-32

Yes

NO

 

 

 

 

 

Table 5. 1: Analog inputs

 

Object

 

Read/

Change- Non-vola-

Linked to

Alarm

Triggers

 

 

 

Object Name

able De-

tile RAM

TR200Pa-

notifi-

Bus Time-

 

 

 

ID

Write

 

 

 

 

scription

Store

rameter

cation

out

 

 

 

 

 

 

 

 

 

 

Terminal

 

 

 

 

 

 

 

 

 

AO:0

42 Output Bus

W/R

Yes

No

6-53

No

Yes

 

 

 

 

Control

 

 

 

 

 

 

 

 

 

 

Pulse out

 

 

 

 

 

 

 

 

 

AO:1

#27 Bus

W/R

Yes

No

5-93

No

Yes

 

 

 

 

Control

 

 

 

 

 

 

 

 

 

 

Pulse out

 

 

 

 

 

 

 

 

 

AO:2

#29 Bus

W/R

Yes

No

5-95

No

Yes

 

 

 

 

Control

 

 

 

 

 

 

 

 

 

AO:3

Analog

W/R

Yes

No

6-63

No

Yes

 

 

 

Out X30/8 [mA]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Analog

 

 

 

 

 

 

 

 

 

AO:4

Output

W/R

Yes

No

26-43

No

Yes

 

 

 

 

X42/7[V]

 

 

 

 

 

 

 

 

 

 

Analog

 

 

 

 

 

 

 

 

 

AO:5

Output

W/R

Yes

No

26-53

No

Yes

 

 

 

 

X42/9[V]

 

 

 

 

 

 

 

 

 

 

Analog

 

 

 

 

 

 

 

 

 

AO:6

Output

W/R

Yes

No

26-63

No

Yes

 

 

 

 

X42/11[V]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 5. 2: Analog outputs

5-2

TR200 BACnet

Page 27
Image 27
Trane BACnet Option Module, TR200 How to Control the Adjustable Frequency Drive, Analog Input and Output Objects