Parameters

 

 

 

 

 

 

 

 

 

 

 

device may have. Please see separate manual TR200 MetasysMG.

 

 

 

12.NX.YY.

 

 

 

 

 

 

 

 

 

[4]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

[9]

FC Option

To be used when a gateway is connected to the integrated RS 485 port,

 

 

 

e.g., the BACnet gateway.

 

 

 

The following changes will take place:

 

 

 

-The address for the adjustable frequency drive port will be set to 1 and

 

 

 

par.8-31Address, is now used to set the address for the gateway on the

 

 

 

 

 

 

 

 

 

 

 

network, e.g., BACnet.

 

 

 

-Baud rate for the Drive port will be set to a fixed value (115,200 Baud)

 

 

 

and par.8-32 Baud Rate is now used to set the baud rate for the network

 

 

 

 

 

 

 

 

 

port (e.g., BACnet) on the gateway.

 

 

 

 

 

 

 

 

 

[20]

 

 

 

 

 

 

NOTE: Further details can be found in the Metasys manual.

8-31 Address

Range:

Function:

1. N/A* [1. - 126. N/A]

Enter the address for the adjustable frequency drive (standard) port.

 

Valid range: 1–126.

 

 

8-32 Baud Rate

Option:

Function:

 

Baud rate selection depends on Protocol selection in par.8-30Protocol.

 

 

 

 

[0]

2400 Baud

[1]

4800 Baud

 

 

 

 

[2]

9600 Baud

[3]

19200 Baud

 

 

 

 

[4] *

38400 Baud

[5]

57600 Baud

 

 

 

 

[6]

76800 Baud

[7]

115200 Baud

Default refers to the FC Protocol.

8-33 Parity / Stop Bits

Option:Function:

Parity and Stop Bits for the protocol par.8-30Protocol using the Adjust- able Frequency Drive Port. For some of the protocols, not all options will be visible. Default depends on the protocol selected.

[0]* Even Parity, 1 Stop Bit

[1]Odd Parity, 1 Stop Bit

[2]No Parity, 1 Stop Bit

[3]No Parity, 2 Stop Bits

TR200 BACnet

6-5

Page 48
Image 48