Trane BACnet Option Module, TR200 8-35Minimum Response Delay, 8-36Max Response Delay, 8-50

Models: TR200

1 56
Download 56 pages 40.28 Kb
Page 49
Image 49
8-35 Minimum Response Delay

Parameters

8-35 Minimum Response Delay

Range:

Function:

10. ms* [5. - 10000. ms]

Specify the minimum delay time between receiving a request and trans-

 

mitting a response. This is used for overcoming modem turnaround

 

delays.

 

 

8-36 Max Response Delay

Range:

Function:

10001. [11. - 10001. ms]

Specify the maximum permissible delay time between transmitting a re-

ms*

quest and receiving a response. Exceeding this delay time will cause

 

control word timeout.

 

 

8-37 Max Inter-Char Delay

Range:

Function:

25.00 [0.00 - 35.00 ms]

Specify the maximum permissible time interval between receiving two

ms*

bytes. This parameter activates timeout if transmission is interrupted.

 

 

8-50

Coasting Select

 

Option:

 

Function:

 

 

 

 

 

Select control of the coasting function via the terminals (digital input)

 

 

and/or via the bus.

 

 

 

[0]

Digital input

Activates Start command via a digital input.

 

 

 

[1]

Bus

Activates Start command via the serial communication port or serial

 

 

communication option.

 

 

 

[2]

Logic AND

Activates Start command via the serial communication bus/serial com-

 

 

munication port, AND additionally via one of the digital inputs.

 

 

 

[3] *

Logic OR

Activates Start command via the serial communication bus/serial com-

 

 

munication port OR via one of the digital inputs.

 

 

 

NOTE: This parameter is active only when par.8-01Control Site is set to [0] Digital and control word.

8-52 DC Brake Select

Option:

 

Function:

 

 

Select control of the DC brake via the terminals (digital input) and/or via

 

 

the serial communication bus.

 

 

 

[0]

Digital input

Activates Start command via a digital input.

 

 

 

[1]

Bus

Activates Start command via the serial communication port or serial

 

 

communication option.

 

 

 

[2]

Logic AND

Activates Start command via the serial communication bus/serial com-

 

 

munication port, AND additionally via one of the digital inputs.

 

 

 

[3] *

Logic OR

Activates Start command via the serial communication bus/serial com-

 

 

munication port OR via one of the digital inputs.

 

 

 

NOTE: This parameter is active only when par.8-01Control Site is set to [0] Digital and control word.

6-6

TR200 BACnet

Page 49
Image 49
Trane BACnet Option Module, TR200 8-35Minimum Response Delay, 8-36Max Response Delay, 8-37Max Inter-CharDelay, 8-50