Parameters

8-53 Start Select

Option:

 

Function:

 

 

Select control of the adjustable frequency drive start function via the ter-

 

 

minals (digital input) and/or via the serial communication bus.

 

 

 

[0]

Digital input

Activates Start command via a digital input.

 

 

 

[1]

Bus

Activates Start command via the serial communication port or serial

 

 

communication option.

 

 

 

[2]

Logic AND

Activates Start command via the serial communication bus/serial com-

 

 

munication port, AND additionally via one of the digital inputs.

 

 

 

[3] *

Logic OR

Activates Start command via the serial communication bus/serial com-

 

 

munication port OR via one of the digital inputs.

 

 

 

NOTE: This parameter is active only when par.8-01Control Site is set to [0] Digital and control word.

8-54 Reverse Select

Option:

 

Function:

 

 

Select control of the adjustable frequency drive reverse function via the

 

 

terminals (digital input) and/or via the serial communication bus.

 

 

 

[0] *

Digital input

Activates Reverse command via a digital input.

 

 

 

[1]

Bus

Activates Reverse command via the serial communication port or serial

 

 

communication option.

 

 

 

[2]

Logic AND

Activates Reverse command via the serial communication bus/serial

 

 

communication port, AND additionally via one of the digital inputs.

 

 

 

[3]

Logic OR

Activates Reverse command via the serial communication bus/serial

 

 

communication port OR via one of the digital inputs.

 

 

 

NOTE: This parameter is active only when par.8-01Control Site is set to [0] Digital and control word.

8-55 Set-up Select

Option:

 

Function:

 

 

Select control of the adjustable frequency drive set-up selection via the

 

 

terminals (digital input) and/or via the serial communication bus.

 

 

 

[0]

Digital input

Activates the set-up selection via a digital input.

 

 

 

[1]

Bus

Activates the set-up selection via the serial communication port or serial

 

 

communication option.

 

 

 

[2]

Logic AND

Activates the set-up selection via the serial communication bus/serial

 

 

communication port, AND additionally via one of the digital inputs.

 

 

 

[3] *

Logic OR

Activate the set-up selection via the serial communication bus/serial

 

 

communication port OR via one of the digital inputs.

 

 

 

NOTE: This parameter is active only when par.8-01Control Site is set to [0] Digital and control word.

TR200 BACnet

6-7

Page 50
Image 50
Trane TR200, BACnet Option Module instruction manual Start Select, Reverse Select, Set-up Select