Parameters

8-56 Preset Reference Select

Option:

 

Function:

 

 

Select control of the adjustable frequency drive Preset Reference selec-

 

 

tion via the terminals (digital input) and/or via the serial communication

 

 

bus.

 

 

 

[0]

Digital input

Activates Preset Reference selection via a digital input.

 

 

 

[1]

Bus

Activates Preset Reference selection via the serial communication port

 

 

or serial communication option.

 

 

 

[2]

Logic AND

Activates Preset Reference selection via the serial communication bus/

 

 

serial communication port, AND additionally via one of the digital inputs.

 

 

 

[3] *

Logic OR

Activates the Preset Reference selection via the serial communication

 

 

bus/serial communication port OR via one of the digital inputs.

 

 

 

NOTE: This parameter is active only when par.8-01Control Site is set to [0] Digital and control word.

8-70 BACnet Device Instance

Range:Function:

1 N/A* [0 - 4194304 N/A]

Enter a unique ID number for the BACnet device.

 

 

NOTE: This parameter is active only when par.8-30Protocol is set to [9] Drive Option.

8-72 MS/TP Max Masters

Range:

 

Function:

 

127 N/

[0 - 127 N/A]

Define the address of the master which holds the highest address in this

A*

 

network. Decreasing this value optimizes polling for the token.

 

 

 

 

NOTE: This parameter is active only when par.8-30Protocol is set to [9]

Option.

 

 

 

 

8-73 MS/TP Max Info Frames

 

Range:

 

Function:

 

 

 

 

1 N/A*

[1 - 65534 N/A]

Define how many info/data frames the device is allowed to send while

 

 

holding the token.

 

 

 

NOTE: This parameter is active only when par.8-30Protocol is set to [9]

Option.

 

 

 

 

 

8-74 "Startup I am"

 

 

 

 

Option:

 

Function:

 

 

 

 

 

 

 

[0] *

 

 

 

 

 

[1]

 

Choose whether the device should send the "I-Am" service message only

 

 

at power-up or continuously with an interval of approx. 1 min.

NOTE: This parameter is active only when par.8-30Protocol is set to [9]

Option.

 

 

 

 

 

8-75

Initialization Password

 

Range:

 

Function:

 

 

 

 

0 N/A*

[0 - 0 N/A]

Enter the password needed for execution of Drive Re-initialization from

 

 

BACnet.

 

 

 

 

 

 

 

NOTE: This parameter is active only when par.8-30Protocol is set to [9] Drive Option.