Trane TR200, BACnet Option Module instruction manual How to Control the Adjustable Frequency Drive

Models: TR200

1 56
Download 56 pages 40.28 Kb
Page 34
Image 34
How to Control the Adjustable Frequency Drive

How to Control the Adjustable Frequency Drive

Object

 

Read /

Change-

Non-vola-

 

Alarm

Object Name

able De-

tile RAM

Drive Par.

notifi-

ID

Write

 

scription

Store

 

cation

 

 

 

 

BV:40

Brake Check

R

No

NA

16-90/00

Yes

BV:41

Pwr. Card Temp

R

No

NA

16-90/01

Yes

BV:42

Ground Fault

R

No

NA

16-90/02

Yes

BV:43

Ctrl.Card Temp

R

No

NA

16-90/03

Yes

BV:44

Ctrl. Word TO

R

No

NA

16-90/04

Yes

BV:45

Overcurrent

R

No

NA

16-90/05

Yes

BV:46

Torque Limit

R

No

NA

16-90/06

Yes

BV:47

Motor TH Over

R

No

NA

16-90/07

Yes

BV:48

Motor TH Over

R

No

NA

16-90/08

Yes

BV:49

Inverter Overld.

R

No

NA

16-90/09

Yes

BV:50

DC undervolt

R

No

NA

16-90/10

Yes

BV:51

DC overvolt

R

No

NA

16-90/11

Yes

BV:52

Short Circuit

R

No

NA

16-90/12

Yes

BV:53

Soft-charge fault

R

No

NA

16-90/13

Yes

BV:54

Line Power Fault

R

No

NA

16-90/14

Yes

BV:55

AMA Not OK

R

No

NA

16-90/15

Yes

BV:56

Live Zero Error

R

No

NA

16-90/16

Yes

BV:57

Internal Fault

R

No

NA

16-90/17

Yes

BV:58

Brake Overload

R

No

NA

16-90/18

Yes

BV:59

U Phase Loss

R

No

NA

16-90/19

Yes

BV:60

V Phase Loss

R

No

NA

16-90/20

Yes

BV:61

W Phase Loss

R

No

NA

16-90/21

Yes

BV:62

Serial Communi-

R

No

NA

16-90/22

Yes

cation Bus Fault

 

 

 

 

 

 

BV:63

24 V Supply Low

R

No

NA

16-90/23

Yes

BV:64

Line Power Fault

R

No

NA

16-90/24

Yes

BV:65

1.8 V Supply Low

R

No

NA

16-90/25

Yes

BV:66

Brake Failure

R

No

NA

16-90/26

Yes

BV:67

Brake IGBT

R

No

NA

16-90/27

Yes

BV:68

Option Changed

R

No

NA

16-90/28

Yes

BV:69

Drive Initialized

R

No

NA

16-90/29

Yes

BV:70

Safe Stop

R

No

NA

16-90/30

Yes

BV:71

Brake Low

R

No

NA

16-90/31

Yes

BV:72

Service Trip P

R

No

NA

16-91/00

Yes

1691/0

 

 

 

 

 

 

BV:73

Service Trip P

R

No

NA

16-91/01

Yes

1691/1

 

 

 

 

 

 

BV:74

Service Trip P

R

No

NA

16-91/02

Yes

1691/2

 

 

 

 

 

 

BV:75

Service Trip P

R

No

NA

16-91/03

Yes

1691/3

 

 

 

 

 

 

BV:76

Service Trip P

R

No

NA

16-91/04

Yes

1691/4

 

 

 

 

 

 

BV:77

No Flow

R

No

NA

16-91/05

Yes

BV:78

Dry Pump

R

No

NA

16-91/06

Yes

BV:79

Curve End

R

No

NA

16-91/07

Yes

Triggers Bus

Timeout

Table 5. 9: Binary values cont.

TR200 BACnet

5-9

Page 34
Image 34
Trane TR200, BACnet Option Module instruction manual How to Control the Adjustable Frequency Drive