Trane BACnet Option Module 8-01, Control Site, 8-02Control Source, 8-03Control Timeout Time

Models: TR200

1 56
Download 56 pages 40.28 Kb
Page 45
Image 45
8-01

Parameters

Parameter Description

8-** Comm. and Options

Parameter group for configuring communications and options.

8-01

Control Site

 

 

 

 

 

Option:

 

Function:

 

 

 

 

 

 

 

 

 

The setting in this parameter overrides the settings in par.8-50Coasting

 

 

Select to par.8-56Preset Reference Select.

 

 

 

 

 

 

 

 

 

[0] *

Digital and ctrl. word

Control by using both digital input and control word.

 

 

 

 

 

 

 

[1]

Digital only

Control by using digital inputs only.

 

 

 

 

 

 

 

[2]

Control word only

Control by using control word only.

8-02 Control Source

Option:Function:

Select the source of the control word: one of two serial interfaces or four

installed options. During initial power-up, the adjustable frequency drive automatically sets this parameter to Option A [3] if it detects a valid serial

communication bus option installed in slot A. If the option is removed,

the adjustable frequency drive detects a change in the configuration, sets par.8-02Control Source back to default setting Adjustable Frequency Drive Port, and the adjustable frequency drive then trips. If an option is

installed after initial power-up, the setting of par.8-02Control Source will not change but the adjustable frequency drive will trip and display: Alarm

67Option Changed.

[0]None

[1]FC RS-485

[2]FC USB

[3]* Option A

[4]Option B

[5]Option C0

[6]Option C1

[30]External Can

NOTE: This parameter cannot be adjusted while the motor is running.

8-03 Control Timeout Time

Range:

Function:

60.0 s* [1.0 - 18000.0 s]

Enter the maximum time expected to pass between the reception of two

 

consecutive messages. If this time is exceeded, it indicates that the serial

 

communication has stopped. The function selected in par.8-04Control

 

 

 

 

 

 

Timeout Function Control Timeout Function will then be carried out.

 

 

 

 

In LonWorks, the following variables will trigger the Control Word Time

 

parameter:

 

nviStartStop

 

nviReset Fault

 

 

 

 

 

6-2

TR200 BACnet

Page 45
Image 45
Trane BACnet Option Module, TR200 instruction manual 8-01, Control Site, 8-02Control Source, 8-03Control Timeout Time