8-06 Reset Control Timeout

Parameters

8-06 Reset Control Timeout

Option:

 

Function:

 

 

This parameter is active only when the choice Hold set-up[0] has been

 

 

selected in par.8-05End-of-Timeout Function.

 

 

 

 

 

 

 

[0] *

Do not reset

Retains the set-up specified in par.8-04Control Timeout Function, [Select

 

 

 

 

 

 

 

set-up 1-4] following a control timeout.

 

 

 

 

 

 

 

[1]

Do reset

Returns the adjustable frequency drive to the original set-up following a

 

 

control word timeout. When the value is set to Do reset [1], the adjustable

 

 

frequency drive performs the reset and then immediately reverts to the

 

 

Do not reset [0] setting.

 

 

 

 

 

 

 

8-07

Diagnosis Trigger

Option:

Function:

 

 

 

This parameter has no function for LonWorks.

 

 

[0] *

Disable

[1]Trigger on alarms

[2]Trigger alarm/warn.

8-10 Control Profile

Option:Function:

Select the interpretation of the control and status words corresponding to the installed serial communication bus. Only the selections valid for the serial communication bus installed in slot A will be visible in the keypad display.

[0]* FC profile

[1]PROFIdrive profile

[5]ODVA

[7]CANopen DSP 402

8-30 Protocol

Option:Function:

[0] *

FC

[1]FC MC

Protocol selection for the integrated FC (standard) Port (RS485) on the control card.

Parameter group 8-7* is only visible when Adjustable Frequency Drive Option [9] is chosen.

Communication according to the FC protocol as described in the TR200 Design Guide, RS 485 Installation and Set-up .

Same as FC [0] but to be used when downloading SW to the adjustable frequency drive or uploading dll file (covering information regarding pa- rameters available in the adjustable frequency drive and their inter- dependencies) to Trane Drive Utility, TDU.

[2]

Modbus RTU

Communication according to the Modbus RTU protocol as described in

 

 

the TR200 Design Guide, RS 485 Installation and Set-up .

 

 

 

[3]

Metasys N2

Communication protocol. The N2 software protocol is designed to be

 

 

general in nature in order to accommodate the unique properties each

 

 

 

6-4

TR200 BACnet