Trane TR200, BACnet Option Module 8-04Control Timeout Function, End-of-TimeoutFunction

Models: TR200

1 56
Download 56 pages 40.28 Kb
Page 46
Image 46
8-04 Control Timeout Function

Parameters

nviControlWord

nviDrvSpeedStpt

nviRefPcnt

nviRefHz

8-04 Control Timeout Function

Option:Function:

Select the timeout function. The timeout function is activated when the control word fails to be updated within the time period specified in par. 8-03Control Timeout Time. Choice [20] only appears after setting the Metasys N2 protocol.

[0] *

Off

[1]Freeze output

[2]Stop

[3]Jogging

[4]Max. speed

[5]Stop and trip

[7]Select setup 1

[8]Select setup 2

[9]Select setup 3

[10]Select setup 4

[20]N2 Override Release

In LonWorks, the timeout function is also activated when the following SNVTs fail to be updated within the time period specified in par.8-03Control Timeout Time:

nviStartStop

nviDrvSpeedStpt

nviReset Fault

nviRefPcnt

nviControlWord

nviRefHz

8-05 End-of-Timeout Function

Option:

 

Function:

 

 

Select the action after receiving a valid control word following a timeout.

 

 

This parameter is active only when par.8-04Control Timeout Function is

 

 

set to [Set-up 1-4].

 

 

 

 

 

 

 

 

 

 

 

[0]

Hold set-up

Retains the set-up selected in par.8-04Control Timeout Function and

 

 

 

 

 

 

 

 

 

displays a warning, until par.8-06Reset Control Timeout toggles. Then

 

 

 

 

 

 

 

the adjustable frequency drive resumes its original set-up.

 

 

 

 

 

 

 

 

 

[1] *

Resume set-up

Resumes the set-up active prior to the timeout.

 

 

 

 

 

 

 

 

 

TR200 BACnet

6-3

Page 46
Image 46
Trane TR200, BACnet Option Module instruction manual 8-04Control Timeout Function, End-of-TimeoutFunction