Chateau™ Decorative Gas Appliance

Fireplace Dimensions

Finished Wall 24¹⁄₂” (622 mm)

 

C

25����

L

for Flush Install 16” (406 mm)

 

(649mm)

3/4" (19mm)

I.D. Minimum Clearance to

 

 

Combustibles

 

 

Standard Framing

 

24���"

 

C

 

 

(622mm)

 

L

 

 

10���"

 

 

 

 

 

 

 

 

(267mm)

Noncombustible Facing

 

 

 

 

Material

 

 

51���" (1299mm)*

3/4"

NOTE: Noncombustible insula-

 

 

 

(19mm)

tion may be placed behind the

 

 

CL Glass

 

 

 

 

facing material.

 

 

25����

 

 

 

 

(649mm)

 

 

 

 

9���"

 

 

 

(235mm)

 

49���"

 

 

Sides and Top

 

 

 

 

(1245mm)

 

 

of Surround

 

 

 

 

 

12���"

 

 

 

 

(311mm)

55"

 

33���"

 

 

29���"

 

 

(1399mm)

(854mm)*

 

 

34���" (876mm)

(746mm)

 

 

 

 

 

 

 

 

32���"

 

 

 

(829mm)

8"

10���" (203mm) 3���" (270 mm)

(98mm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1/2"

 

 

 

 

 

 

 

 

 

 

5/8" (16mm) 5���" (143mm)

 

 

 

 

 

 

 

 

 

 

1���"

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(13mm)

 

 

 

 

 

37���" (962mm)

 

 

 

 

 

 

 

 

 

 

 

(35mm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6" (152mm) 44���" (1121mm) 1" (25mm)

*When framing unit on outside wall, flush with the wall,

a 1/4" (6mm) clearance must be allowed on both sides and top of surround.

Fig. 2 Fireplace specifications and framing dimensions for DVT38S2.

NOTE: The control box must be located within the same room as the fireplace.

Mantel Surround Framing

3 x 12 Control Box Spacer

 

48���"

11/16"

 

(1222 mm)

 

 

(17 mm)

Framing

 

24���"

Cross Piece

(613 mm)

 

C

 

 

L

 

 

 

 

45���"

Critical

(1149 mm)

 

Dimension

 

CAUTION: If you are framing with the plan to use the CHFN0495, CHWC495, CHFPR495 surround mantel, it is extremely critical to meet the dimen- sions provided, especially if the mantel is not available at the time of framing. A framing stud is allowed to be placed on the inside of the 6” (152

mm)standoff on the side of the unit where the conduit is located to meet the 24¹⁄₈” ( 613 mm) critical dimension from the center of the unit.

The unit is certified with a 3” (76 mm) standoff (to combustible) on the side of the unit where the con- duit is located, therefore; it is permissible to locate stud on the inside of the standoff at 3” (76 mm) from the body of the unit. (Fig. 2a)

3“ (76 mm)

FP1479

NOTE: The 6” (152 mm) standoff is sent out with the unit for the purpose of making the glass symmetrical with respect to the overall width of the unit.

Fig. 2a Framing dimensions are critical when framing for the surround mantel CHFN0495, CHWC495, CHFPR495.

4

20009543

Page 4
Image 4
Vermont Casting DVT38S2 installation instructions Standard Framing, Mantel Surround Framing, Critical, Dimension