Windster 100 manual Two-Post Center-Mount Rack Kit Installation

Models: 100

1 24
Download 24 pages 20.43 Kb
Page 1
Image 1

Dell™ PowerApp.web 100 and

PowerApp.cache 100 Appliances

Rack Installation Guide

This installation guide provides instructions for trained service technicians installing one or more Dell PowerApp™ 100 appliances in a rack. This guide includes proce- dures for the following three rack kits:

Two-post center-mount

Two-post flush-mount

Four-post rack cabinet

One rack kit is required for each PowerApp 100 system to be installed in the rack.

Two-Post Center-Mount Rack Kit Installation

This procedure provides instructions for installing a Dell PowerApp 100 appliance in a two-post open-frame relay rack, such as those found in telecommunications equip- ment facilities. Both 3-inch and 6-inch wide two-post racks are accommodated.

The two-post open-frame relay rack must be properly secured to the floor, to the ceil- ing or upper wall, and where applicable, to adjacent racks, using floor and wall fasteners and bracing specified or approved by the rack manufacturer or by industry standards. Refer to the two-post open-frame relay rack manufacturer’s installation documentation for precautionary warnings and information before attempting this installation.

CAUTION: Do not attempt to install the PowerApp system into a two-post open-frame relay rack that has not been securely anchored in place. Dam- age to the system and personal injury may result.

Refer to “Safety Instructions” at the front of this document for additional safety infor-

mation regarding rack installation.

support.dell.com

Dell PowerApp 100 Appliances Rack Installation Guide

1

Page 1
Image 1
Windster 100 manual Two-Post Center-Mount Rack Kit Installation