The ACCB is
WARNING: Electrical Hazard
Do not remove or alter in any way the
WARNING: Fire Hazard
A possible fire hazard can exist if 120 Vac only sources (such as inverters and generators) are wired incorrectly into 120/240 Vac distribution panels containing multiwire branch circuits.
Accessing the Terminal Blocks
Consult the Sine Wave Plus Inverter/Charger Owner’s Manual for additional information on wire and disconnect requirements.
To prepare the ACCB and Inverter for wiring installation:
1.Expose the terminal block in the ACCB by removing the ACCB cover, as described on page
2.Expose the terminal block in the inverter by removing the AC access cover, as described in your inverter’s owner’s guide.
Wire Sizes and Disconnect Requirements
◆Determine the wire sizes and disconnect sizes required for the installation. See Table
Important: Only use copper conductors rated for 75 °C (167 °F).
Table
| Full | Maximum | Cable Size |
|
| Fuse/Breaker | Required in | ||
| Capability | Required | Conduit | |
|
|
|
|
|
| 60 Amps | 60 Amps | #6 AWG (THHN) | |
|
|
|
|
|
|
|
|