
Installation
The distribution blocks in the ACCB AC terminal block accept the following gauge wires.
•The 1:1 distribution blocks accept #2/0 - 14 AWG.
•The 1:4 distribution blocks accept #2/0 - 14 AWG on the single terminal and
The ground bar in the ACCB accepts #4 to 14 AWG wires.
1:1 distribution block |
|
|
| 1:4 distribution block |
|
|
| ||
|
|
|
| |
|
|
|
| (x3) |
Figure
Table
Wire Gauge | Torque Value | |
|
| |
14 - 10 AWG | 20 | |
8 AWG | 25 | |
6 | - 4 AWG | 36 |
4 | - 2/0 AWG | 50 |
|
|
|
WARNING: Electrical Hazard
Be sure to connect the ground wires first when connecting AC wiring to prevent a potential shock hazard.
CAUTION: Equipment Damage
The inverter’s AC output must never be wired to the utility or generator output. This will cause severe damage to the inverter which is not covered under warranty.
Important: These instructions assume that the DC connections have already been made and that the system ground has already been established. Consult the Sine Wave Plus Owner’s Manual for additional wiring information.
Important: Be sure to use